Break Tank Cold Water Booster Sets
GHV1-4 Hydrovar Variable Speed
1
Operating, Installation and Maintenance Instructions
EC Declaration of conformity
Xylem Water Solutions UK Limited declare that the GHV Booster set conforms to the requirements of the
Machinery Safety Directive
2006/42/EC.
Electromagnetic compatibility (EMC) Directive
2014/30/EU
Conforming to the UK Health & Safety Requirements
2008 No. 1597
Water supply (Water fittings) regulations
1999
Signed:
Position:
Engineering manager
Date:
20-04-2016 Revision B
Clive Willmot
t
Introduction
This leaflet contains information to enable the safe installation and operation of the products mentioned.
The following instructions must be read and understood by all persons responsible for the installation, operation
and maintenance of this product.
Warning Symbols
Safety instructions where noncompliance would affect safety.
Safety instructions where electrical hazard is involved.
Safety instructions where noncompliance could cause damage to the equipment.
Instruction for safe use
This product has been designed for boosting cold water in potable water installations to the
operating conditions shown.
This product should not be installed until this leaflet has been studied carefully and understood.
Handling, transportation and installation of this equipment should only take place with the proper
use of lifting equipment. This product must be stored in a frost-free dry environment.
50Hz 2900 min-1
LpA (dB+/-2) SV Pumps
P2 (KW)
1 Pump
2 Pump
3 Pump
4 Pump
2.2
<70
<70
<70
<70
3
<70
<70
<70
<70
4
<70
<70
<70
<70
5.5
<70
<70
<70
<70
7.5
71
74
76
77
11 - 22
73
76
78
79
Noise Emissions
Operating limits
Fluid temperature
0˚C to 40˚C
Ambient temperature
0˚C to 40˚C
Operating pressure
Max 8bar, 10bar, 16bar depending on set type
Protection class
Motor and Electrical panel
IP55
Hydrovar
IP55
Summary of Contents for Lowara GHV1
Page 4: ...4 ...