Sending a 4-20 mA input signal to the drive using an-
alog input 53. You will wire your 4-20 mA signal into
terminal 53 and common on terminal 55. Analog in-
put 53 accepts only 4-20 mA.
Sending a 0-10 V input signal to the drive using ana-
log input 54. You will wire your 0-10 V signal into ter-
minal 54 and common on terminal 55. Analog input
54 can accept current or voltage signal, by default it
is set to 0-10 V.
U
I
A DIP switch located behind the MCO 301 card allow
to change the analog input 54 setting.
To change the analog input 54 setting from voltage
to current follow the steps below:
• Power off the drive
• Remove LCP control panel
• Remove MCO301 card
• Change the DIP switch setting from U (0-10 V) to I
(4-20 mA)
3 Operation
3.1 Operating instructions
en - Original instructions