IMPORTANT NOTICE!

 

This device should be installed by a qualified electrician in 

accordance with the latest edition of the IEE wiring regulations.

 

Due to our policy of continual product improvement Xulux reserves the right 

to alter the specification of this product without prior notice.  

FM 45789  

EMS 534520  

detection pattern

 

LOAD  

 

8 Amp resistive and incandescent lighting  

4 Amp fluorescent lighting  

3 Amp compact fluorescent lighting  

3 Amp low energy lighting  

3 Amp low voltage lighting (switch primary of transformer)  

3 Amp fans and ventilation equipment  

Switch SON lighting loads via a contactor

 

 

SUPPLY VOLTAGE

 

 

220 -240 Volts AC 50 Hz  

TIME OUT PERIOD

 

 

Adjustable 10s to 30m  

LIGHT LEVEL

 

 

 

Light to dark  

 

TERMINAL CAPACITY

  

2.5 mm

2

 

MATERIAL

 

 

 

Flame retardant ABS  

TYPE

   

 

 

Class 2  

TEMPERATURE

 

 

-10°C to 35°C  

CONFORMITY  

 

 

EMC -89/336/EEC  

 

 

 

 

LVD -73/23/EEC  

specification  

description and operation

 

BT-PIR108

 

Ceiling PIR Presence Detector

 

The BT-PIR108 presence detector is designed to provide automatic control of lighting, heating or ventilation 

loads.  It detects movement using a PIR sensor and turns the load on. When an area is no longer oc-

cupied the load will switch off after an adjustable time out period.

 

 

An adjustable internal light sensor provides additional energy saving in lighting applications. When an 

area is occupied lighting is only switched on when the level of natural light is below a preset level. 

 

 

When the unit is first powered up the PIR sensor will always detect immediately regardless of whether 

the room is occupied.   

wiring diagram

 

dimensions

 