VESDA-E VES-A10-P Product Guide
64
www.xtralis.com
l
Holidays:
The settings used to define a holiday period. Use the dropdown calendars to choose the
start and end times of the holiday (or break) period. Night time thresholds are used during the holiday
period.
5.5.7
Airflow Options
The Airflow options provide the ability to set:
l
limits for what the detector considers to be normal airflow behavior for the sampling pipe network
l
which pipe inlets are being used
l
aspirator speed
These settings should be confirmed in the ASPIRE design of the sampling pipe network.
Note:
Refer to Section 5.6 for the default settings.
Figure 5-18: Airflow Options
The Airflow configuration options are as follows:
l
Air Flow:
The air flow conditions, as a percentage of the normalized air flow, that will cause a fault to be
reported. If the installation site flow conditions vary significantly, it is recommended that the Major High
and Major Low parameters are set closer to their limits.
l
Major High:
The level of air flow considered to be so far above normal as to require urgent attention.
l
Minor High:
The level of air flow considered to be above normal but not urgent.
l
Minor Low:
The level of air flow considered to be below normal but not urgent.
l
Major Low:
The level of air flow considered to be so far below normal as to require urgent attention.
l
Significant Flow Change:
The amount of airflow change at which an event is recorded in the event log.
l
Delay:
The length of time between the air flow fault threshold being reached and the fault relay operation.
l
Valve Test:
The time interval between automatic tests of the scanning valves.
l
Pipes in Use:
The pipes that are actually being used. Refer to Section 3.3 on page 17 for further
information.
l
Aspirator:
Select the required Aspirator Speed setting 1 through 10, as determined using ASPIRE.
Summary of Contents for VESDA-E VES-A10-P
Page 2: ......
Page 10: ...VESDA E VES A10 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 22: ...VESDA E VES A10 P Product Guide 16 www xtralis com This page is intentionally left blank ...
Page 52: ...VESDA E VES A10 P Product Guide 46 www xtralis com This page is intentionally left blank ...
Page 82: ...VESDA E VES A10 P Product Guide 76 www xtralis com This page is intentionally left blank ...
Page 86: ...VESDA E VES A10 P Product Guide 80 www xtralis com This page is intentionally left blank ...
Page 103: ...VESDA E VES A10 P Product Guide www xtralis com 97 Figure 7 21 Undo Sampling Module screws ...
Page 108: ...VESDA E VES A10 P Product Guide 102 www xtralis com ...
Page 110: ...VESDA E VES A10 P Product Guide 104 www xtralis com This page is intentionally left blank ...
Page 114: ...VESDA E VES A10 P Product Guide 108 www xtralis com This page is intentionally left blank ...
Page 120: ...VESDA E VES A10 P Product Guide 114 www xtralis com This page is intentionally left blank ...
Page 126: ...VESDA E VES A10 P Product Guide 120 www xtralis com Z zone 57 58 81 115 ...