ICAM by Xtralis
ICAM IFT-P Product Guide
www.xtralis.com
19
A
Input-Output Modules
ICAM IFT-P detectors have 5 relays fitted as standard. The I/O functionality may be extended by adding I/O
modules. These plug onto the standard I/O module in a stackable chain of up to 3 positions. They are
recognized by the processor as Modules 1 to 3 going from left to right. When installing new modules, the type
must be entered in the Setup menu in order to be correctly recognized. Some modules, such as the 4 Channel
Relay Module, can be individually programmed under Configuration mode.
A.1
4-Channel Relay Module
Relay module is configured using Xtralis VSC.
The optional Remote display may also be used as follows:
1. After installing the relay module check that MOD1 in the Engineering menu has now changed to 1.
(This is different for other types of cards)
2. In Setup menu, change MOD1 to 1 (if using a different card use the number that appears in the
Engineering menu).
3. In the Configuration menu set MOD1 to a number from 1 to 6 representing the triggering event where:
1 = Alert
2 = Action
3 = Fire1
4 = Fire2
5 = Flow fault
6 = General Fault
All four relays on the card will now activate for this event with respect to their corresponding sector.
Figure A-1: Relay Module
Single pole double throw (SDPT) contacts are used in the relay modules with a rating of 2 A at 24 VDC.