VESDA by Xtralis
VESDA VLI Product Guide
www.xtralis.com
23
A+
A-
B-
Shield
Module 1
Module 2
Module 3
Module 5
Module 4
Shield
B+
A+
A-
B-
Shield
Shield
B+
A+
A-
B-
Shield
Shield
B+
A+
A-
B-
Shield
Shield
B+
A+
A-
B-
Shield
Shield
B+
(VLI-885)
Figure 3-11: Example closed loop VESDAnet network
The VLI-885 detector is shipped with the VESDAnet A and B terminals looped. Remove the A and B links prior
to connecting the detector to the VESDAnet. If the detector is not to be networked with other devices, then do
not remove the A and B links.
Note:
For each VLI-885 detector connected on VESDAnet, ensure that the shield link wire (supplied) is
retained as shown by the dotted line in Figure 3-11. The link wires [A+ to B+] and [A- to B-] (not
shown in the figure but supplied for stand-alone operation) should be removed. On other VESDAnet
devices all the link wires are removed when connected on VESDAnet.
Shield
A-
A+
Shield
B-
B+
Figure 3-12: Closed loop for standalone detectors with VESDAnet capability
Note:
Refer to the VESDA Communications Guide for further information.