Xmart STA-16A User Manual Download Page 2

 

USER MANUAL - STA 16A 

 

___________________________________________________________________________________________________________________________________ 

 

www.xmart-ups.com 

 

1701-STA-16 220V- EN 

-  

2

 

2. INSTALATION 

      

 

This product can be installed in a 19" rack cabinet or over a flat surface as well. 
In case of installing in a rack cabinet, please below instructions. 
 

 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
1. Install according to above figure. 
2. Connect input "A" in input socket "A" in rear panel. 
2. Connect input "B" in input socket "B" in rear panel. 
4. Connect protected products to STA-16A outlets. Note there are multiple outlets with 10A capacity and 1 outlet with 16A capacity. 
 
 

3. OPERATION 

 

      

 

OPERATION PANEL:  

 

 

 
 

 
 
1. Selector for main input: 

Selects the preferred input. 

2. Preferred Input LED:

 Indicates what is the preferred or pre-selected input (A or B) 

3. Status Input LED: Indicates status for each input 

 

LED A: ON: Input "A" OK 

 

LED A: OFF: Input "A" OFF (no voltage) 

 

LED A: Blinking (intermitent): Input "A" voltage is out of range (low or high input) 

 

LED B: ON: Input "B" OK 

 

LED B: OFF: Input "B" OFF (no voltage) 

 

LED B Blinking (intermitent): Input "B" voltage is out of range (low or high input) 

4. Output LED: Indicates what input is connected to the output 

 

LED A: ON: Output connected to input "A" 

 

LED B: ON: Output connected to input "B" 

5. Alarm LED: Alarma indicator 
6. Alarm Mute 

 
OPERACION:  

 
TURN-ON: 

After connecting all input and output cables, just activate input switches A and B to ON position. 

 
SELECTING PREFERRED INPUT: 

Select preferred input by button "1" in front panel. Default preferred input is "A". 

 

 

USER MANUAL - STA 16A 

 

___________________________________________________________________________________________________________________________________ 

 

www.xmart-ups.com 

 

1701-STA-16 220V- EN 

-  

3

 

4. COMMUNICATION PORTS

 

 

      

 

 

USB*: USB communication using dedicated software. Pin 1: VBUS / Pin 2: D- / Pin 3: D+ / Pin 4: GND 

 

RS-232*: Serial communication using dedicated software. Pin 2: TX / Pin 3: RX / Pin 5: GND / Pin 6: +12Vdc 

 

Relays outputs port 

 * 

check 

software 

manual. 

 

RELAY OUTPUTS PORT 

It is used to provide status information about AC inputs and STA-16A situation according to following figure. 
 

 
 
 
 
 
 

 
 
 
 

 

 

Pin 1: Common point. 

 

Pin 2: Close = Output connected to input "B" 

 

Pin 3: Close = Output connected to input "A" 

 

Pin 4: Close = Input "A" OK 

 

Pin 5: Close = Input "B" OK 

 

Pin 6: Close = Device OK 

 
 
 

5. TECHNICAL SPECIFICATIONS

 

 

      

 

 

 

ATS 16A - 220V

16A

Capacity / Capacidad (VA):

16A @ 220V (3.500VA)

Input / Entrada

Voltage / Voltaje (VAC)

220/230/240Vac

Range / Rango (VAC)

180 - 258 Vac

Frequency / Frecuencia (Hz)

50 / 60Hz

Max Input Current / Corriente Max:

16 Amps

Inlets / Tomacorrientes de Entrada

2 x IEC C20

Output / Salida

Voltage / Voltaje (VAC)

220/230/240Vac

Power Outlets / Tomacorrientes de Salida

8 x IEC-C13 (10 Amps) + 1 x IEC-C19 (16 Amps)

Protections / Protecciones

Overload & Shortcircuit / Sobrecarga & 
Cortocircuito

AC Breaker for each input / Disyuntor AC para cada entrada

Transfer Time / Tiempo de Transferencia

Transfer Time / Tiempo de Transferencia

4 - 8 ms

Size & Weight / Características Físicas

Size / Dimensiones (cm)

330x483x44 mm

Net Weight / Peso Neto (Kg.)

5,0

Gross Weight / Peso Bruto (Kg.)

6,0

Operating Conditions / Ambientales

Temperature / Temperatura

0-40°C

Humidity / Humedad

< 90% (no condensing)

Noise / Ruido

< 40dB

Reviews: