INDEX
USER MANUAL - OPTIMA RT10 6K/10K
www.xmart-ups.com
VER.161205-GA2 (ENG)
7
4.
INSTALLATION
This section of the manual covers installation procedure and instructions for this UPS series. Before doing installation you must
revise and understand sections related to safety and site conditions.
SAFETY INSTRUCTIONS
WARNING: Before revising this section you must read and understand very well section 1 of this manual: “GENERAL SAFETY
INSTRUCTIONS”.
WARNINGS, RECOMMENDATIONS AND LIABILITY LIMITATION
REACH AND LIABILITY LIMITATION:
The preparation of the site, wiring and all protection devices must be supplied by end user and it will
not be responsibility neither the UPS distributor nor the UPS technician in charge of the start-up.
The place will be conditioned be end user or electrical contractor and must fulfill with local normative and directives and UPS technical
requirements.
This manual describes minimal conditions and technical requirements with which the site must accomplish.
Directives and requirements described in this manual, do not pretend to substitute in any way local electrical directives or normative.
In some cases, local directives or regulations might be more exigent than UPS technical requirements described by this manual. In that
case end user electrical contractor must be sure to comply with all related local electrical regulations and directives.
Installation and start-ups MUST be done by qualified personnel only complying with safety procedures.
This kind of equipment has been designed to provide electrical output even when it is not powered-on.
UPS output could be energized even when UPS is turned-off in case external bypass is activated.
Internal or external battery banks always can generate risk of electrical shock because high DC voltage.
External battery banks must be revised before connecting them to UPS to confirm their DC voltage is compatible with this UPS.
DC polarity of the Battery bank must be revised to confirm it is OK before connection. A reverse polarity can generate permanent
damage in batteries and UPS.
This UPS is rated as “Class I” so it is recommendable to connect GROUND terminal to the EARTH before making any other connect
ions.
Before making AC input connections, technicians must confirm all switches of input lines are in open state (OFF).
All installation instructions of this manual must be complied.
All local electrical regulations must be complied.
Power lines must be protected by protection devices against over current (breakers) or leak currents with capacity and technology
appropriate to effectively accomplish its function. Moreover, installation grounding must be correct.
Install the UPS in well ventilated locations and leave room enough between UPS and close objects and structures
Do not connect to UPS equipment or devices that exceed its capacity, this would overload the UPS.
This product has been designed to be used indoors protected from water, direct sun light, dust and extreme temperature.
Do not put any object on the UPS; do not apply any force over UPS. Do not cover UPS ventilation.
This UPS must be connected to appropriate electrical service according to selected model. Technical specs sticker in the UPS shows
the UPS power ratings. DO NOT connect this UPS to any of its own power outlets, this could damage the unit permanently.
Do not connect AC motor based equipment without a careful sizing of the UPS based on inrush current instead of average current.
Inrush current typical of motor based system could overload this UPS.
We strongly recommend to place a warning sign on main electrical board to avoid external personnel manipulate AC lines during
revision and start-up work is performed.