AM100 Series User Guide
www.milesight-iot.com
23
7.3 Downlink Commands
AM100 series sensors support downlink commands to configure the device. Application
port is 85 by default.
Appendix
Default LoRaWAN Parameters
DevEUI
2
nd
to 11
th
digits of SN
e.g. SN = 61 26 A1 01 84 96
Then Device EUI = 24E124126A101849
AppEUI
24E124C0002A0001
Appport
0x55
NetID
0x010203
DevAddr
The 5
th
to 12
th
digits of SN
e.g. SN = 61 26 A1 01 84 96 00 41
Then DevAddr = A1018496
AppKey
5572404C696E6B4C6F52613230313823
07
7d
(
CO
2
)
67 04
67 04 => 04 67 =1127
CO
2
= 1127 ppm
08
7d(TVOC)
07 00
07 00 => 00 07=7
TVOC = 7 ppb
09
73
(
Barometric
Pressure
)
68 27
68 27=>27 68=10088
Pressure=10088*0.1=1008.8hPa
Channel
Type
Data Example
Description
ff
03(Set Reporting Interval)
b0 04
b0 04 => 04 b0 = 1200s
18 (Enable/disable
sensor)
01 01
(Enable
Temperature)
Byte 1: Select Sensor
01: Temperature
02: Humidity
03: PIR
04: Light
05: CO
2
06: TVOC
07: Barometric Pressure
Byte 2: 00=disable, 01=enable