Operating instructions
The DINgate TM module can setup a remote IP link to a connected RS485 device.
The IR supports the industry-standard protocol DLMS-COSEM for configuration purposes. This protocol implements
the SMR5 application layer.
The DINgate module gives visual feedback on its working state by its 2 Status LED Indicators:
6.1
PWR
–
POWER Status LED
–
Red LED
•
Not lit:
DINgate module is not powered
•
Blinking:
DINgate module is powered, but not (yet) able to readout the connected RS485 device
•
Lit:
DINgate module is powered, and has readout the connected RS485 device
6.2
WAN
–
Network Status LED
–
Green LED
•
Not lit:
The DINgate module is not connected to a radio network.
This may have one of the following causes
-
No or wrong SIM card (disabled)
-
No network coverage
-
Modem is defect
•
Blinking:
The DINgate module is registered to the radio network
No end to end data session with the head-end system can be established.
•
Lit:
The DINgate module is registered to the radio network and a PDP context was established.
This means the module got an IP address from the network and the head-end system is
able to establish a data connection with the module.
The nominal state of the network status LED
is ‘LED Lit’
This means the module can always be reached on its IP address by the head-end system.