Default Settings and Ranges
975-0240-01-01
B–3
Inverter Menu
Charger Menu
Item
Default Setting
Range
Step
Size
24 V
Nominal
48 V
Nominal
24 V Nominal
48 V Nominal
Low Batt Cut Out
22V
44V
20–24V
40–48V
1V
LBCO Delay
10s
0–600s
1s
High Batt Cut Out
32.0V
70.0 V
29.0–36.0V
58.0–70.0V
0.1V
Search Watts
50W
25–255W
5W
Search Delay
2s
1–25s
1s
Item
Default Setting
Range
Step Size
24 V
48 V
24 V
48 V
Batt Type
Flooded
Flooded, Gel, AGM, Custom
n/a
Batt Capacity
440Ah
50–2000Ah
1Ah
Max Chg Rate
100%
10–100%
1%
Charge Cycle
2-Stage
2-Stage, 3-Stage
n/a
Default Batt Temp
Warm
Cold, Warm, Hot
n/a
ReCharge Volts
25.0V
50.0V
20.0–27.0V
40.0–54.0V
0.1V
Absorb Time
180min
1–480min
1min
Chg Block Start
n/a
12:00 AM–11:59 PM,
00:00–23:59
n/a
Chg Block Stop
n/a
12:00 AM–11:59 PM,
00:00–23:59
n/a