Basic Installation Procedures
975-0784-01-01
19
AC breakers and fuses must be sized to adequately protect the
wiring that is installed on the input and output AC circuits of the
Freedom XC. All breakers and wiring must be sized and
connected in accordance with the electrical codes or regulations
applicable to your installation.
wiring sizes based on the U.S. National Electrical Code and the
Canadian Electrical Code. These examples are based on using a
two-conductor-plus-ground copper cable rated at 60
°
C, and
assuming an ambient temperature of up to 30
°
C. Ensure that your
breakers and fuses have suitable temperature ratings for your
wiring. Other codes and regulations may also be applicable to your
installation.
Breaker Size (A)
10A
15A
20A
30A
Minimum Wire
Size (AWG)
14AWG
14AWG
12AWG
10AWG
Table 4 Required AC Wire Size vs Breaker Rating
AC Output Neutral Bonding
The neutral conductor of the Freedom XC’s AC output circuit (that
is, AC Output Neutral) is automatically connected to the safety
ground during inverter operation. When AC utility power is present
this connection is not present, so that the utility neutral (that is,
AC Input Neutral) is only connected to utility ground at your
source. This conforms to the National Electrical Code (NEC),
which requires that separately derived AC sources (such as
inverters and generators) have their neutral conductors tied to
ground in the same way that the neutral conductor from the utility
is tied to ground in only one place. Check the regulations for your
specific application to ensure that the installation will comply with
the necessary requirements. In other words, the AC Input Neutral
ground bonding and Output Neutral ground bonding must be
isolated from each other.
AC Grounding
As per UL458 SA29.5, for all permanently connected marine
inverters: The Freedom XC should be connected to a grounded,
metal, permanent wiring system. Also, make sure that an AC
ground wire is connected to the AC ground terminal on the unit. Do
not just connect the line and neutral wires.
All connections to the unit shall comply with all regulations,
directives, local codes and ordinances.
Summary of Contents for Freedom XC 1000
Page 1: ...Freedom XC Inverter Charger Owner s Guide Freedom XC 1000 817 1050 Freedom XC 2000 817 2080 ...
Page 6: ...This page is intentionally left blank 2 ...
Page 22: ...This page is intentionally left blank 2 ...
Page 28: ...This page is intentionally left blank 2 ...
Page 56: ...This page is intentionally left blank 2 ...
Page 98: ...This page is intentionally left blank 2 ...