Inverter Overload Operation
975-0390-01-01
41
Inverter Overload Operation
This graph shows how long (measured in milliseconds) the
Freedom HF will operate for a given output current (measured in
Amps).
Both the Freedom HF 1000/1055 models and Freedom HF
1500/1800 models are represented in the illustration below.
The graph illustrates surge operation at 25 °C.
0
10
12
14
16
18
20
30
40
50
200
400
600
800
1000
1200
1400
1600
4000
Freedom HF 1000/1055
Freedom HF 1500/1800
Time (ms)
Output Current (amps)
Invert Power Derating vs.
Ambient Temperature
If the unit is in inverter mode and in elevated ambient temperature
above 25 °C, you will have to reduce power draw according to the
following chart to avoid over-temperature shutdown.
25
30
35
40
45
50
750
800
850
900
1000
@12.5 volts
30°C
900 watts
800 watts
750 watts
850 watts
~33°C
@11.5 volts
Freedom HF 1000/1055
watts
°C