Installation
System 182-XT-4
3 - 42
ba75753e06
12/2014
3.10
Connections to the relay and current outputs
3.10.1 General installation instructions
WARNING
If external electrical circuits that are subject to the danger of
physical contact are incorrectly connected to the relay contacts,
there may be a danger of life threatening electric shock. Electrical
circuits are regarded to be subject to the danger of physical
contact when there are voltages higher than the Safety Extra Low
Voltage (SELV).
Pay attention to the following points during installation:
Electrical circuits subject to the danger of physical contact
must only be connected by a qualified electrician.
Electrical circuits subject to the danger of physical contact
must only be connected when they are voltage-free.
If electrical circuits subject to the danger of physical contact
are switched with a relay, no circuit that is not subject to this
danger (e. g. the DIQ/CHV module) may be operated on the
further relays.
Switching voltages and switching currents on the relay
contacts must not exceed the values specified in
chapter 9 T
. Protect electrical circuits against
currents that are too high with an electrical fuse.
Only single-phase consumers can be switched with the relays.
Under no circumstances must multiphase consumers be
switched with the aid of several relays (example three-phase
current driven pumps). Always switch multiphase consumers
via a protective relay.
The DIQ/S 182-XT-4 may only be opened after the installation if
all external voltages have been previously switched off.
Connections
The DIQ/S 182-XT-4 has a total of five current outputs and six relay
outputs which are spread across the two terminal strips in the DIQ/
S 182 XT-4. The terminal strips are shown in section 3.13.
Materials required
Wire end sleeves, suitable for the connecting wires, with suitable
crimping tool
1 x cable gland, matched to the cable diameter (see section 3.8 on
page 3-33).
Tools
Cable stripping knife
Wire stripper
Phillips screwdriver
Small screwdriver
Summary of Contents for DIQ/S 182-XT-4
Page 6: ...Contents System 182 XT 4 0 4 ba75753e06 12 2014 ...
Page 14: ...Safety System 182 XT 4 2 4 ba75753e06 12 2014 ...
Page 68: ...Installation System 182 XT 4 3 54 ba75753e06 12 2014 ...
Page 86: ...Operation System 182 XT 4 4 18 ba75753e06 12 2014 ...
Page 92: ...The SETTINGS menu System 182 XT 4 5 6 ba75753e06 12 2014 ...
Page 128: ...Maintenance and cleaning System 182 XT 4 7 2 ba75753e06 12 2014 ...
Page 144: ...Technical data System 182 XT 4 9 12 ba75753e06 12 2014 ...
Page 146: ...Accessories and options System 182 XT 4 10 2 ba75753e06 12 2014 ...
Page 150: ...Appendix store separately if required System 182 XT 4 12 2 ba75753e06 12 2014 ...
Page 151: ......