Original Operating Instructions
BATI0XXX-ES-1-ZZZ-1
Appendix
O_BATI_0XXX-ES-1-ZZZ-1_V1.4_GB
Seite
57
von
60
11.2 Technical Data
11.2.1 Electrical Data
Table 7: Electrical data
BATI0600-ES-1-270-1
BATI0720-ES-1-300-1
BATI0900-ES-1-380-1
Remarks
AC SIDE
Max. rated apparent power
600 kVA
720 kVA
900 kVA
At rated grid voltage
Rated active power
500 kW
615 kW
770 kW
At (cos
(φ)) = 1.0
Rated grid voltage
270 V, 3~, 50 Hz
300 V, 3~, 50 Hz
380 V, 3~, 50 Hz
Other values on request
Grid configuration
IT-grid
Max. output current
1283 A
1385 A
1367 A
Max. short-circuit current
50 kA
Line power factor (cos φ)
> 0,98
At > 20 % of rated power
AC-current distortion (THD)
< 3 %
DC SIDE
Battery side nominal voltage
750 V
Max. battery voltage
890 V
Min. battery voltage
450 V
500 V
630 V
Battery side currents
+/- 1136 A
+/- 1360 A
+/- 1400 A
Battery side max. short-circuit
current
6,4 kA
Battery side current THD
< 3 %
Battery side number of DC
Inputs
1
General
Control strategy
CC-CV, Power controlled, Island mode
Efficiency in %
(97.1|97.5|97.5|97.3|97.1)
(97.4|97.9|97.9|97.7|97.5)
(97.6|98.0|98.0|97.8|97.6)
At (10|30|50|75|100) % power
Standby losses (at night)
< 30 W
Maximum auxiliary power
< 1000 W
+ heating power (optional)
Measuring accuracy
Grid frequency
+/- 40 mHz
Average value of 8 grid
periods
Summary of Contents for BAT1200-ES-2-270-1
Page 60: ......