13. trouBLeshootInG
When generator engine fails to start after several attempts, or if no electricity is available at the output
socket, check the following chart.
If your generator still fails to start or to generate electricity, contact your nearest Robin dealer shop for
further information or corrective procedures.
when enGIne fAILs to stArt:
Check fuel level.
If empty, refill fuel tank making sure not to
overfill.
Check if the key switch of the engine is in the
good position.
Turn the key switch to “ON” position and then
press Start button on the display.
Check to make sure generator is not connected
to an appliance.
If connected, turn off the power switch on the
connected appliance and unplug.
Check the voltage of the battery
Must be over 12V.
Check if the supply wires of the fuel solenoid
and the oil sensor are well connected.
Reconnect the wires if necessary.
when no eLectrIcItY Is GenerAteD At receptAcLe:
Check to make sure no-fuse breaker is in the ‘‘l’’
(ON) position.
After making sure that the total wattage of the
electrical appliance is within permissible limits
and there are no defects in the appliance, turn
the no-fuse breaker to the ‘‘l’’ (ON) position.
If breakers continue to actuate, consult your
nearest servicing dealer.
Check AC terminals for loose connection.
Secure connection if necessary.
Check to see if engine starting was attempted
with appliances already connected to generator.
Turn off switch on the appliance, and disconnect
cable from receptacle. Reconnect after generator
has been started properly.