7.2.7 Checking the external blocking
The external blocking input inhibits e. g. the function of the high set element of the phase current.
For this purpose the parameter "Blocking Function" in the menu "Signal input blocking" for the high set ele-
ment must be set to "Yes". Then the terminals 14 and 17 are supplied with auxiliary voltage
(e.g. 110 V DC).
The time delay tI> should be set to EXIT for this test. Inject a test current which could cause a high set (I>>)
tripping. Observe that there is no trip and alarm for the high set element.
Remove the auxiliary supply voltage from the blocking input. Inject a test current to trip the relay (message
„TRIP“ on the display). Interrupt the test current.
7.2.8 Checking the input "Fast trip"
The "Fast trip" function allows the unit to be tripped within the shortest possible time. A prerequisite for cor-
rect tripping is the correct setting of the parameters. In the menu "Signal input - fast trip" the setting should
be "instantaneously“. If a current is now injected which is greater than the lowest adjustable overcurrent
threshold and an auxiliary voltage (110 V DC) is supplied to the terminals 32 and 33, tripping takes place in-
stantaneously (tl>=50 ms ±10 ms).
7.2.9 Remote trip
Checking the input "Remote trip" does not require any test current. The terminals 20 and 22 are provided
with supply voltage (230 V AC ±20%). This leads to tripping within 200 ms.
Caution!
These terminals may only be supplied with voltage for a maximum of 2 min.
7.2.10 Test of input „External Reset“
For testing this function, voltage is to be applied to terminals 14 and 15. The relay is activated now by it-self
and in the display appears „External reset activated“.
7.2.11 Checking the battery
The battery test is carried out by pressing the key <DISPLAY ON>. If the display indicates "Protection pa-
rameter", the battery is ok.
Note:
Relays which have been out of order for more than one month might show "Battery voltage too low" on the
display when the key <DISPLAY ON> is first pressed. The reasons for this are that, on the one hand, the ca-
pacitors are completely discharged and, on the other hand, the long storage time of the battery.
But before replacing the battery the power supply has switched off and the <DISPLAY ON> key is pressed
again. If "Battery voltage too low" is indicated again, the battery does need replacing.