Display if a minimum current is exceeded:
When C.T. current is available, the relay is activated at the smallest possible phase current. Displayed are
automatically date and time.
In this mode measuring values can be called at any time.
Display after tripping:
If the relay has tripped, the internal power supply is disconnected and only the LED flashes. By pressing
<DISPLAY ON>, the relay is re-connected. The tripping values are displayed after pressing the
<SELECT/RESET> push button.
>>>>>>FAULT<<<<<
>>>>Memory_1<<<<
6.1.2 Display
The menu of the data displayed can be subdivided into five groups:
Measuring
values
Protection
parameters
Kind of tripping/relay assignment
System
parameters
Signal input parameters
Fault
memory
Relay
test
The fault memory consists of five individual stores of identical configuration.
For changing from the main menu to the first of the submenus, the <SELECT/RESET> push button is shortly
to be pressed. From here the single groups can be selected via push buttons <+> and
<->. To proceed to any of the individual menu points, push button <SELECT/RESET> is to be pressed.
6.1.3 Setting procedure
After a parameter value has been selected, it can be adjusted to the required value by push buttons <+> and
<->.
6.1.4 Parameter setting by using the password
When the <ENTER> push button has been pressed, the following information is displayed:
>>>>Parameter<<<
store_value_?___
If the changed value is to be saved, the <ENTER> push button has to be pressed again shortly.
Now the display is shows:
>>>>Parameter<<<
Password:_xxxx__