Manual 37187A
SYNCONpanel - Transportable Remote Synchronizing Panel
Discrete Inputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
To use the GCP-31/
RPQ
+
SC08
for a mobile system like described, discrete inputs are required.
CAUTION
Please note that the maximum voltages, which may be applied at the discrete inputs are defined as fol-
lows. Voltages higher than those specified destroy the hardware!
Maximum input range: +/-4 to 40 Vdc.
Terminal Associated
common
Description
(according to DIN 40 719 Part 3, 5.8.3)
A
max
3
Automatic 1
2.5 mm²
5
Automatic 2
2.5 mm²
53
7
Enable MCB (mains circuit breaker)
2.5 mm²
4
Reply: GCB is open
2.5 mm²
54
7
Reply: Mains power circuit breaker is open or mains parallel status (in
items with 1 CB)
2.5 mm²
Table 3-1: Terminal assignment - discrete inputs
To monitor a phase rotation relay, the alarm input [D03] must be used.
If it is required to block an automatic mains failure start, the discrete input [D11] must be programmed to "Inhibit
emergency run".
Terminal Associated
common
Description
(according to DIN 40 719 Part 3, 5.8.3)
A
max
36 33
Discrete input [D03] "Phase rotation check O.K.":
This control input is evaluated if the busbar is energized. In case of a
failure, the message "Phase sequence" is displayed and closing the cir-
cuit breakers is blocked. If the busbar phase rotation shall not be
monitored, this input must be energized permanently.
2.5 mm²
68 60
Discrete input [D11]
- Alarm input or
- Inhibit emergency run
2.5 mm²
Table 3-2: Terminal assignment - discrete inputs