Manual 37259C
SPM-D11 - Synchronizing Unit
© Woodward
Page 37/79
LC Display
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
15
LC-Display
LC-Display
Performance values can be monitored from the two-line display, pro-
vided that the control is in automatic mode. In configuration mode,
the individual parameters are displayed.
Display Monitoring in Automatic Mode: Double Voltage / Frequency Display
LCD type 1
(V configured)
B: 000 V 00.00Hz
G: 000 V 00.00Hz
LCD type 2
(kV configured)
B:00,0kV 00.00Hz
G:00,0kV 00.00Hz
Double voltage and double frequency displays, Generator values
The generator and synchronization voltage and -frequency are displayed. The phase
angle between the generator and synchronization voltage is displayed by the syn-
chroscope (LED strip).
B
........Synchronization voltage and frequency
G
.......Generator voltage and frequency
LCD type 1
(V configured)
Gen 000V i0.95
000A 000kW
LCD type 2
(V configured)
Gen 00,0kV i0.95
000A 000MW
Generator values
Generator values are monitored:
G
.......Generator values
•
upper line:
- Line voltage L1-L2
- phase angle
•
bottom line:
- current L1
- Real power
Display Monitoring in Automatic Mode: Alarm Indication
----------------
xxxxxxxxxxxxxxxx
Alarm indication, bottom line
The indications are displayed according to the following list:
Type of alarm
Displayed text
Synchronization time is exceeded
Synchr. time
Wire break 0/4-20mA input for set point value
Wirebreak P
set.
Generator underfrequency
Gen. underfrequency.
Generator overfrequency
Gen. overfrequency.
Generator undervoltage
Gen.undervoltage.
Generator overvoltage
Gen.overvoltage.
Generator overload
Gen.overload.
Generator reverse-/-reduced load
Reverse/reduced load.