Operation Manual 37107F
MFR 3 - Multi Function Relay
© Woodward
Page 55/165
Chapter 6.
Configuration
Configuration can be performed via the front panel push buttons and LC display or using a PC and the LeoPC1
program with the serial interface. Additionally it is possible to configure the unit via CAN bus. The following
baud rates apply to each method:
•
Direct configuration
9,600 Baud (8 bit, no parity, 1 stop bit)
•
CAN bus configuration
125 kBaud
CAUTION
Please note that configuration only should be performed when system is not operating.
Generator voltage must not be connected during configuration and the DI "Configuration blocked"
(terminal 34) must be de-energized.
Code level 2 access is required to select between direct configuration or configuration via CAN.
NOTE
Refer to Appendix B for a complete list of parameters at the end of this manual.