3.3
Parameter Settings
Description
Information
Corrective Action
Problems with the transfer of device parameters from one
protection device to another of the same type (e. g. MCA4).
You have configured the parameters of a HighPROTEC
device. Now you want to transfer these parameters to
another device. This is possible if both devices are of
the same type, e. g. MCA4.
Read out the device parameters with Smart view from the first
device. Save them into a file.
Now reopen this file with Smart view. Adapt the settings to the
order code of the second device by selecting [Edit / Modify
Device Configuration (Typecode)...]. Select »Apply«. By this the
existing parameter file is being converted to the format of the
second device.
Now there may be implausible parameters. These are marked
with a question mark and are not valid for this device type.
Please adapt the values of the implausible parameters.
Afterwards you can transfer the parameter settings to the
second device.
15
Troubleshooting Guide
HPT-3.6-EN-TSG
3 Problems with the Device
3.3 Parameter Settings