Communication Protocols
IEC61850
IEC61850
Introduction
To understand the functioning and mode of operation of a substation in an IEC61850 automation environment, it is
useful to compare the commissioning steps with those of a conventional substation in a Modbus TCP environment.
In a conventional substation the individual IEDs (Intelligent Electronic Devices) communicate in vertically direction
with the higher level control center via SCADA. The horizontal communication is exclusively realized by wiring
output relays (OR) and digital inputs (DI) among each other.
In an IEC61850 environment communication between the IEDs takes place digitally (via Ethernet) by a service
called GOOSE (Generic Object Oriented Substation Event). By means of this service information about events is
submitted between each IED. Therefore each IED has to know about the functional capability of all other connected
IEDs.
Each IEC61850 capable device includes a description of it's own functionality and communications skills (IED
Capability Description, *.ICD).
By means of a Substation Configuration Tool to describe the structure of the substation, assignment of the devices
to the primary technique, etc. a virtual wiring of the IEDs among each other and with other switch gear of the
substation can be done. A description of the substation configuration will be generated in form of a *.SCD file. At
last this file has to be submitted to each device. Now the IEDs are able to communicate closed among each other,
react to interlockings and operate switch gear.
Commissioning steps for a conventional substation with
modbus TCP environment:
•
Parameter setting of the IEDs
•
Ethernet installation
•
TCP/IP settings for the IEDs
•
Wiring according to wiring scheme
Commissioning steps for a substation with IEC61850
environment:
1. Parameter setting of the IEDs
Ethernet installation
TCP/IP settings for the IEDs
2. IEC61850 configuration (software wiring)
a) Exporting an ICD file from each device
b) Configuration of the substation
(generating a SCD file)
c) Transmit SCD file to each device
327
MCDLV4
DOK-HB-MCDLV4-2E
IED1
IED2
IED3
IEC61850
Master
Ethernet
Sc
ad
a
IE
C
61
85
0
GOOSE IEC61850 soft wiring
IED1
IED2
IED3
Modbus-TCP
Master
Ethernet
Sc
ad
a
M
od
bu
sT
C
P
Conventional hard wiring
DI
BO
DI
BO
DI
BO
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...