System Alarms
Global Protection Parameter of the Demand Management
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of
module/stage.
inactive,
active
inactive
[SysA
/General
Settings]
ExBlo Fc
Activate (allow) or inactivate (disallow)
blocking of the module/stage. This
parameter is only effective if a signal is
assigned to the corresponding global
protection parameter. If the signal becomes
true, those modules/stages are blocked that
are parameterized "ExBlo Fc=active".
1..n,
Assignment List
-.-
[SysA
/General
Settings]
Alarm
Alarm
inactive,
active
inactive
[SysA
/Power
/Watt]
Threshold
Threshold (to be entered as primary value)
1 -
40000000kW
10000kW
[SysA
/Power
/Watt]
t-Delay
Tripping Delay
0 - 60min
0min
[SysA
/Power
/Watt]
Alarm
Alarm
inactive,
active
inactive
[SysA
/Power
/VAr]
Threshold
Threshold (to be entered as primary value)
1 -
40000000kVAr
10000kVAr
[SysA
/Power
/VAr]
t-Delay
Tripping Delay
0 - 60min
0min
[SysA
/Power
/VAr]
Alarm
Alarm
inactive,
active
inactive
[SysA
/Power
/VA]
Threshold
Threshold (to be entered as primary value)
1 -
40000000kVA
10000kVA
[SysA
/Power
/VA]
245
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...