Technical Data
Boot phase
After switching on the power supply the protection will be available in approximately 9 seconds.
After approx. 28 seconds the Protection Communication is active (provided the fiber optic connection and
configuration of both devices is correct).
After approximately 2 minutes (depending on the configuration) the boot phase is completed (HMI and
communication initialized).
The “ProtCom” communication becomes active some seconds later than the
protection becomes active, therefore the backup overcurrent protection module
is active during this time.