Technical Data
Voltage and Residual Voltage Measurement
The following Technical Data apply to 18-pole (combined) terminals. These terminals offer in addition to the voltage
measurement inputs also output relays or digital inputs.
Nominal voltages:
60 - 200 V (can be configured)
Max. measuring range:
300 V AC
Continuous loading capacity:
300 V AC
Power consumption:
at Vn = 100 V S = 22 mVA
at Vn = 110 V S = 25 mVA
Frequency range:
50 Hz or 60 Hz
±
10%
Terminals:
Screw-type terminals
Frequency Measurement
Nominal frequencies:
50 Hz / 60 Hz
1141
MCDLV4
DOK-HB-MCDLV4-2E
0,56 - 0,79 Nm
5-7 lb·in
0,3 Nm
2.65 lb·in