Service and Commissioning Support
Forcing Analog Inputs*
* = Availability depends on ordered device.
The parameters, their defaults, and setting ranges have to be taken from
Analog Inputs section.
Principle – General Use
The User MUST ENSURE that the Analog Inputs operate normally after
maintenance is completed.
For commissioning purposes or for maintenance, Analog Inputs can be set by force.
Within this mode [Service/Test Mode (Prot inhibit)/WARNING! Cont?/Analog Inputs], Analog Inputs can be set by
force:
Permanent; or
Via timeout.
If they are set with a timeout, they will only keep their “Forced Value” as long as this timer runs.
If the timer
expires,
the Analog Input will operate normally.
If they are set as »
Permanent«, they will keep the “Forced Value”
continuously. This menu will show the current value that is fed to the Analog Input until the User activates the force
mode by calling up the »
Function«. As soon as the force mode is activated, the shown value will be frozen as long
as this mode is active. Now the User can force the Analog Input value. As soon as the force mode is deactivated,
measured value will be shown again.
1118
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...