Modbus-
Address
CAN
Mux
CAN
Byte
Size
Index
Description
Unit
Scale
Model
Internal
Mask: 2000h
06.36 Pole slip
Mask: 1000h
All
07.33 FRT Time-dep. voltage 3
Mask: 0800h
All
Internal
Mask: 0400h
Internal
Mask: 0200h
07.31 FRT Time-dep. voltage 2
Mask: 0100h
All
Internal
Mask: 0080h
Internal
Mask: 0040h
Internal
Mask: 0020h
08.40 CAN J1939 device 3 timeout
Mask: 0010h
All
08.39 CAN J1939 device 2 timeout
Mask: 0008h
All
08.38 CAN J1939 device 1 timeout
Mask: 0004h
All
08.37 CAN J1939 ECU timeout
Mask: 0002h
All
08.29 CANopen error interface 3
Mask: 0001h
All
50218
72
5-6
int16
Internal
50219
73
1-4
int32
2526
Generator negative reactive energy
Mvarh *100
All
50221
73
5-6
int16
Internal
50222
74
1-4
int32
05.70 Active power set point ramped
kW
*1
All
50224
74
5-6
int16
Internal
50225
75
1-4
int32
05.92 Reactive power set point ramped
kvar
*1
All
50227
75
5-6
int16
Internal
75 Mux x 20ms = 1.5s refresh rate
9.2.7
Protocol 5016 (Basic Visualization)
Modbus-
Address
Size
Index
Description
Unit
Scale
Model
50000
int16
Protocoll-ID, always 5016
50001
int16
3181
Skaling Power (16 bits) Exponent 10x W
(5;4;3;2)
All
50002
int16
3182
Skaling Volts (16 bits) Exponent 10x V
(2;1;0;-1)
All
50003
int16
3183
Skaling Amps (16 bits) Exponent 10x A (0;-1)
All
50004
Internal
50005
Internal
50006
Internal
50007
Internal
Topic AC Generator and Busbar values
991
easYgen-3000XT Series
B37574
9 Appendix
9.2.7 Protocol 5016 (Basic Visualization)
Released