Remote
control
parameter
Availability with supported ECU number ...
Comment
1
2
3
4
5
6
7
8
9
10
11
12
The bit will be reset, if the
critical mode has been
expired or aborted.
Engine
power
mode
No
No
No
No
No
No
No
No
No
No
Yes
No
This message is generated
according to parameter
"ECU power mode"
(parameter
Engine
selected
application
No
No
No
No
No
No
No
No
No
No
Yes
No
This message is generated
according to parameter
"ECU application"
(parameter
).
1
Please contact manufacturer to clarify whether both frequencies (50/60 Hz) may be
controlled by the speed bias.
2
In case the rated speed of the easYgen and the ECU don't match, please make sure
that the CAN connections works and change parameter
3
Speed biasing signal is transmitted as absolute value.
4
Speed biasing signal is transmitted as Offset value.
7.5.3
Device Types "Standard" and "Standard C"
General notes
If the used ECU is not specific listed in the chapter
(EMR3 & EMR4), John Deere, Daimler, Perkins, Iveco, Caterpillar, Liebherr, etc.) we
recommend to configure the "Device type" (parameter
) to the setting
Standard. Visualization via J1939 is working with every J1939 ECU. Concerning remote
control most ECUs are also supporting the speed biasing via J1939 standard message
TSC1. This chapter supplies you with the details of the device type standard, to help you
to clarify with the manufacturer how the ECU is supported.
Displayed messages (visualization)
In standard mode, the easYgen is able to display all values listed in the table
“Standard visualization messages”
if they are supported by the connected ECU.
Diagnostic trouble codes (DM1/DM2)
In standard mode, the easYgen diagnostic messages DM1 (Active Diagnostic Trouble
Codes) and DM2 (Previously Active Diagnostic Trouble Codes) are displayed. It is also
possible to reset DM1 and DM2 failure codes via DM3 and DM11 messages.
Remote control messages
The following table shows the transmitted remote control messages. These messages are
only transmitted if the parameter "ECU remote controlled" (parameter
) is
configured to "On".
840
easYgen-3000XT Series
B37574
7 Interfaces And Protocols
7.5.3 Device Types "Standard" and "Standard C"
Released