ID
Parameter
CL
Setting range
[Default]
Description
Off
Monitoring is disabled.
2663
Delay
2
1 to 999 s
[30 s]
If one of the above mentioned
conditions for an operating range
failure is fulfilled, an alarm will be
issued. If the respective condition
is not fulfilled anymore before the
delay time expires, the delay time
will be reset.
2661
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class B]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
2662
Self acknowledge
2
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
Table 80: Operating Range Failure settings
4.5.6.20 Load Share Interface Redundancy is Lost
General
Beside the automatic handling of redundant load share line messages the easYgen can
inform the operator if a redundant load share communication line get lost. Preassumption
for that is an enabled redundant load share line like CAN/Ethernet A in conjunction with a
successful system update procedure.
If the according alarm has occurred the operator usually checks the "Diagnostic devices"
screen. Available on device display or over ToolKit. There he will be informed which
channel is affected. Refer to system update for more information.
Function
If the parameter "9924 Load share interface" is configured to "CAN/Ethernet A" and the
system update was executed, the monitoring becomes active.
The devices observes if the both load share messages are correctly received. If a channel
fails the alarm "LS interf. redundancy" is triggered.