ID
Parameter
CL
Setting range
[Default]
Description
the time configured here, the
monitoring sequence will be reset.
4991
4992
4993
4994
4995
4996
4997
Point 1 voltage
[x = 1 to 7]
2
0.0 to 200.0%
4991: [10.0%]
4992: [10.0%]
4993: [90.0%]
4994: [90.0%]
4995: [90.0%]
4996: [90.0%]
4997: [90.0%]
The voltage values of time-
dependent voltage 2 monitoring
voltage points are configured
here.
Notes
Please avoid a setting between
0.1% and 5.0%.
4981
4982
4983
4984
4985
4986
4987
Point 1 time
[x = 1 to 7]
2
0.00 to 320.00 s
4981: [0.00 s]
4982: [0.15 s]
4983: [1.50 s]
4984: [10.00 s]
4985: [20.00 s]
4986: [30.00 s]
4987: [40.00 s]
The time values of time-
dependent voltage 2 monitoring
time points are configured here.
4.5.3.10.3 Time Dependent Mains Voltage Monitor 3
The Time dependent voltage monitoring 3 is an additional independent FRT monitoring,
which behaves like the Time dependent voltage monitoring 1 described in the previous
chapter.
It serves a LogicsManager command variable 11750 "07.33 Time-dep. voltage 3" to trip a
relay or to incorporate the monitoring into the mains decoupling feature of the device.
The alarm class and the self-acknowledge feature is taken from the original time
dependent voltage monitoring (see
╚═▷ “General settings for Mains decoupling and
Time-dep. voltage 3
ID
Parameter
CL
Setting range
[Default]
Description
9130
Monitoring
2
On
Enabling the time-dependent
voltage monitoring 3. It is an
additional independent FRT
monitoring. It serves a
517
easYgen-3000XT Series
B37574
4 Configuration
4.5.3.10.3 Time Dependent Mains Voltage Monitor 3
Released