The display indicates "Mains
settling" during this time.
4.5.3.2
Blocking of Mains Protection
General notes
The operator can deactivate the mains monitoring features and the decoupling function.
A dedicated LogicsManager is installed to disable all mains monitoring and the decoupling
function.
Already latched alarms (self acknowledge = No) are not removed from the alarm list by
this function.
Following functions are blocked:
• Mains decoupling
•
• Mains over frequency 1&2
•
• Mains under frequency 1&2
•
• Mains over voltage 1&2
•
• Mains under voltage 1&2
•
• Mains voltage increase (10 minutes average value)
•
• Mains Time-dependent Voltage (FRT)
•
• Mains Q(V) Monitoring
•
• Mains phase shift
•
• Mains df/dt
•
ID
Parameter
CL
Setting range
[Default]
Description
15159
Disable mns.mon.
2
Determined by LogicsManager
87.72
[(0 & 1) & 1]
t
ON
= 0.00; t
OFF
= 0.00]
= 11461
Switch to disable
• all mains monitoring
•
functions and
• the mains decoupling
•
function.
486
easYgen-3000XT Series
B37574
4 Configuration
4.5.3.2 Blocking of Mains Protection
Released