ID
Parameter
CL
Setting range
[Default]
Description
before the delay expires the time
will be reset.
2453
Activation frequency
2
15 to 85 Hz
[20 Hz]
The speed/frequency mismatch
monitoring is enabled at this
generator frequency.
2451
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class E]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
2452
Self acknowledge
4
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
2458
Enabled
4
Always
Monitoring for this fault condition
is continuously enabled.
[87.70 LM:Eng.mon]
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
4.5.2.4
Engine Start Failure
General notes
If it is not possible to start the engine within a configured number of start attempts (refer
to
╚═▷ “4.4.1.2 Engine Start/Stop”
), an alarm will be initiated.
473
easYgen-3000XT Series
B37574
4 Configuration
4.5.2.4 Engine Start Failure
Released