ID
Parameter
CL
Setting range
[Default]
Description
For additional information refer to
2377
2383
Self acknowledge
2
4
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
2378
2384
Enabled
2
Always
Monitoring for this fault condition
is continuously enabled.
[87.70 LM:Eng.mon]
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
4.5.1.6.2
Miscellaneous
4.5.1.6.2.1 Generator Ground Fault (Level 1 & 2)
General notes
The generator ground fault is determined differently depending on the following
configuration options:
• Mains current input is configured for mains current
•
(calculated ground fault)
• Mains current input is configured for ground current
•
(measured ground fault)
459
easYgen-3000XT Series
B37574
4 Configuration
4.5.1.6.2 Miscellaneous