ID
Parameter
CL
Setting range
[Default]
Description
2407: [Class E]
Notes
For additional information refer to
2402
2408
Self acknowledge
2
4
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
2403
2409
Enabled
2
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
4.5.1.5.5
Load sharing
Active power load sharing mismatch
ID
Parameter
CL
Setting range
[Default]
Description
5100
Monitoring
2
On
Load share monitoring is carried
out according to the following
parameters.
[Off]
Monitoring is disabled.
4841
Limit
2
1.0 to 100.0%
[30.0%]
The percentage value that is to be
monitored for the threshold limit is
defined here.
If this value is reached or
exceeded for at least the delay
time without interruption, the
action specified by the alarm class
is initiated.
449
easYgen-3000XT Series
B37574
4 Configuration
4.5.1.5.5 Load sharing
Released