ID
Parameter
CL
Setting range
[Default]
Description
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
4.5.1.5.3
Generator Reverse/Reduced Power (Level 1 & 2) ANSI# 32R/F
General notes
The power produced by the generator is calculated from the voltage and current values
measured in accordance with how parameters "Generator voltage measuring"
(parameter
) and "Generator current measuring" (parameter
) are
configured.
The generator power limits may be configured for reduced power and/or reverse power
depending on the threshold values entered. The note below explains how a reduced or
reverse power limit is configured.
If the single-phase or three-phase measured real power is below the configured limit of
the reduced load or below the configured value of the reverse power, an alarm will be
issued.
If this protective function is triggered, the display indicates "Gen. rev./red. pwr.1" or
"Gen. rev./red. pwr.2" and the logical command variable "06.12" or "06.13" will be
enabled.
╚═▷ “9.1.1 Triggering Characteristics”
for the triggering characteristic of this
monitoring function.
Definition
• Reduced power Fault initiated if the monitored real power falls below the configured
•
(positive) limit.
• Reverse power Fault initiated if the direction of the monitored real power reverses
•
and the configured (negative) limit is exceeded.
Configuration examples
The values for reverse /reduced power monitoring can be configured as follows:
• Level 1 limit = Positive and Level 2 limit = Positive
•
(whereas Level 1 limit > Level 2 limit > 0 %)
• Both limits are configured for reduced power monitoring.
•
444
easYgen-3000XT Series
B37574
4 Configuration
4.5.1.5.3 Generator Reverse/Reduced Power (Level 1 & 2) ANSI# 32R/F