ID
Parameter
CL
Setting range
[Default]
Description
= 11914
DI 6 is pre-assigned by default to
this function, but may be
configured freely.
For information on the
LogicsManager and its default
settings see
.
5718
MCB open time pulse
2
0.10 to 9.90 s
[1.00 s]
This time defines the length of the
MCB open time pulse, if the
automatic switch unblocking MCB
is activated.
12974
MCB open in MAN
2
Determined by LogicsManager
87.48
[(0 & 1) & 1]
= 11437
With the rising edge of this
LogicsManager equation a MCB
open command in operating mode
MANUAL is initiated. The state
TRUE of this LM inhibits the MCB
close command in MANUAL.
Notes
This parameter only applies to
application mode
A04
.
For information on the
LogicsManager and its default
settings see
.
12975
MCB close in MAN
2
Determined by LogicsManager
87.49
[(0 & 1) & 1]
= 11438
With the rising edge of this
LogicsManager equation a MCB
close command in operating mode
MANUAL is initiated.Precondition:
deactivated "MCB open in MAN"
Notes
This parameter only applies to
application mode
A04
.
For information on the
LogicsManager and its default
settings see
.
4.4.3.5
Configure Breakers: Synchronization
General notes
The following parameters are only applicable for application modes
A03
A04
.
ID
Parameter
CL
Setting range
[Default]
Description
5728
Synchronization
mode
2
Off
The synchronization is disabled;
the frequency and voltage
289
easYgen-3000XT Series
B37574
4 Configuration
4.4.3.5 Configure Breakers: Synchronization
Released