ID
Parameter
CL
Setting range
[Default]
Description
1203
Enabled
2
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
4.4.2.3
Discrete Outputs (LogicsManager)
The discrete outputs are controlled via the LogicsManager.
For information on the LogicsManager and its default settings see
Some outputs are assigned a function according to the application mode (see following
table).
Relay
Application mode
No.
Terminal
None
A01
GCB open
A02
GCB
A03
GCB/MCB
A04
[R 01]
41/42
LogicsManager; pre-assigned with 'Ready for operation OFF
CAUTION! Only relay [R 01] has an inverse logic. The relay opens (all other relays close), if
the logical output of the LogicsManager becomes TRUE.
[R 02]
43/46
LogicsManager; pre-assigned with 'Centralized alarm (horn)'
[R 03]
44/46
LogicsManager; pre-assigned with 'Starter'
[R 04]
45/46
LogicsManager; pre-assigned with 'Diesel: Fuel solenoid, Gas: Gas valve'
[R 05]
47/48
LogicsManager; pre-assigned with 'Preglow'
[R 06]
49/50
LogicsManager
Command: close GCB
[R 07]
51/52
LogicsManager
Command: open GCB
[R 08]
53/54
LogicsManager
Command: close
MCB
[R 09]
55/56
LogicsManager
Command: open
MCB
[R 10]
57/60
LogicsManager; pre-assigned with 'Auxiliary services'
[R 11]
58/60
LogicsManager; pre-assigned with 'Alarm class A, B active'
238
easYgen-3000XT Series
B37574
4 Configuration
4.4.2.3 Discrete Outputs (LogicsManager)
Released