ID
Parameter
CL
Setting range
[Default]
Description
will be performed. The engine will
go directly to rated speed.
4.4.2
Inputs And Outputs
4.4.2.1
Function Of Inputs And Outputs
4.4.2.1.1
Discrete Inputs
The discrete inputs may be grouped into two categories:
• Programmable
•
◦ The discrete input has been assigned a default function using either the
◦
LogicsManager or preconfigured alarms such as "emergency stop".
◦ The following sections describe how these functions are assigned.
◦
◦ The function of a discrete input can be changed if required.
◦
◦ The following description of the inputs, labeled with "programmable", refers to
◦
the preconfiguration.
• Fixed
•
◦ The discrete input has a specific function that cannot be changed depending
◦
upon the configured application mode.
Input
Type/Preset
Description
Discrete input [DI
01]
Programmable
Preconfigured to "Emergency STOP"
This discrete input is configured as alarm class F and is
not delayed by the engine speed.
Discrete input [DI
02]
Programmable
Preconfigured to "Startrequest in
AUTO"
Enabled in the AUTOMATIC operation mode
This discrete input is configured as a Control input in the
alarm class and is not delayed by the engine speed.
• Energized
•
If the unit is in the AUTOMATIC operation mode
(selected with the operating mode selection push
button on the front panel) the controlled engine is
started automatically.
• De-energized
•
The engine is stopped.
Discrete input [DI
03]
Programmable
Preconfigured to "Low oil pressure"
This discrete input is configured as alarm class B and is
delayed by the engine speed.
Discrete input [DI
04]
Programmable
Preconfigured to "Coolant
temperature"
This discrete input is configured as alarm class B and is
not delayed by the engine speed.
228
easYgen-3000XT Series
B37574
4 Configuration
4.4.2 Inputs And Outputs
Released