Configuring a Set Point Control via Analog Input
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The following example illustrates how to configure an easYgen for using an external load set point via analog in-
put [AI 03]. The external set point may be enabled using a switch, wired to discrete input [DI 04] (configure pa-
rameter 1262 “Alarm class” to control). An analog 0 to 20 mA input is to be used where 4 mA corresponds with
0 % power (0 MW), 12 mA corresponds with 50 % power (1 MW), and 20 mA corresponds with 100 % power
(2 MW).
Configuring the Rated Generator Power
From the main screen on the unit select Parameter -> Configuration -> Measurement config. and configure the
following parameter:
ID
Parameter
Value
Comment
1752
Gen. rated active power [kW]
2000
Generator rated power of 2 MW
Table 4-2: Configuration of the rated generator power
Configuring the Analog Input for Real Power Set Point
From the main screen on the unit select Parameter -> Configuration -> Application config. -> Inputs/outputs con-
fig. -> Analog inputs config.-> Analog input 3 and configure the following parameters:
ID
Parameter
Value
Comment
1100
Type
Linear
A user-defined linear characteristic curve is to be used
1101
User defined min display value +00000
A value of 000.00 % is displayed at the minimum of the input range
1102
User defined min display value +10000
A value of 100.00 % is displayed at the maximum of the input range
1139
Sender value at display min.
020.00%
The sender value at minimum display is 20 % i.e. 4 mA
1140
Sender value at display max.
100.00%
The sender value at maximum display is 100 % i.e. 20 mA
1120
Sender type
0 - 20mA
A 0 to 20 mA sender is used on the analog input
1103
Monitoring wire break
Low
If the analog signal falls below 2 mA, a wire break is indicated
1104
Wire break alarm class
Class B
An alarm of class B will be issued in case of a wire break
1105
Self acknowledge wire break
No
A wire break is not automatically cleared after it has been repaired
10116 Filter time constant
Off
No filter time constant is applied to the analog signal
3636
Bargraph minimum
+00000
The start value for the bargraph display of the analog input is 00000
3637
Bargraph maximum
+10000
The end value for the bargraph display of the analog input is 10000
Table 4-3: Configuration of the analog input for real power set point
The following parameters may only be changed using ToolKit and serve for a more detailed display of the analog
value:
ID
Parameter
Value
Comment
1125
Description
ActivePower SP (%) Analog input [AI 03] is labeled with "ActivePower SP (%)" on the display
1135
Value format
000.00%
The value format of the bargraph display of the analog input is "000.00%"
Table 4-4: Configuration of the analog input for real power set point - ToolKit only parameters
Configuring the Load Controller
The load controller is to be configured that it uses a fixed load setpoint 1 of 2 MW unless a switch energizes dis-
crete input [DI 04] for enabling a variable load setpoint 2, which is controlled by analog input [AI 03].
From the main screen on the unit select Parameter -> Configuration -> Application config. -> Controller config. -
> Load control config. and configure the following parameters:
ID
Parameter
Value
Comment
5539
Load setpoint 1 source
05.04 Internal pwr. setp.1 Internal power setpoint 1 is used as setpoint 1
5526
Load setpoint 1
Constant
A constant load is to be controlled for setpoint 1
5520
Int. load control setpoint 1 02000.0kW
A constant load of 2 MW is to be used for internal setpoint 1
5540
Load setpoint 2 source
06.03 Analog input 3
Analog input 3 is used as setpoint 2
5527
Load setpoint 2
Constant
A constant load is to be controlled for setpoint 2
Table 4-5: Configuration of the load controller