Application Mode {2oc}
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
This application mode may be used for mains parallel operation. In this case, the easYgen will function as an en-
gine control with generator, mains and engine protection. The control unit can open and close the GCB and the
MCB.
An emergency mode (AMF operation) is only possible in this application mode.
Figure 2-4: Application mode {2oc}
The easYgen requires in all application modes the feedback reply from the circuit breakers. These replies are
used to define, whether it controls frequency, shares the load with other gensets, or performs active load control.
The following feedback signals and commands are used in this application mode and fixed to the respective dis-
crete inputs and outputs:
•
DI 7 "Reply MCB" (mains parallel)
•
DI 8 "Reply GCB" (normally closed (break) contact)
•
DO 6 "Command: GCB close"
•
DO 7 "Command: GCB open"
•
DO 8 "Command: MCB close"
•
DO 5 "Command: MCB open"