Wolf LL-114 Instructions Download Page 1

LL-366 Issue 3 26/03/09

 

 

 

 

 

 
Wolf ATEX GRP Transformer  
Operation and Maintenance Instructions

  

Please Retain – Read Before Use 
Models 
LL-114, LL-114/RIG, LL-114/RB, LL-114/CEAG,  
LL-214, LL-214/RIG, LL-214/RB, LL-214/CEAG, LL-221 

 

EC Declaration of Conformity 

 

The Wolf ATEX Transformer meets all relevant provisions of the 94/9/EC 
Explosive Atmospheres (ATEX Equipment) Directive by virtue of the issued 
EC type examination certificate, demonstrating compliance with all relevant 
harmonised standards and essential health and safety requirements. 
 
The Wolf ATEX Transformer has a 400 VA maximum load, and is housed in a 
durable GRP enclosure enclosed in a Stainless Steel Skid.  The Transformer 
is approved as Group II, equipment for use in zone 1 & 2 potentially explosive 
gases, vapours, mists and dusts where the T3 temperature class permits.  

 

 
Approval Codes/Certification:  

 

II 2 GD Ex ed IIC T3 IP66  

 

 

  Ex td A21 IP66 T200ºC  

-20 to +55ºC  
Supply Voltages: 230VAC or  6%-10%  

 

Output Voltage 110VAC or 24VAC 

 

EC Type examination certificate: 

SIRA02ATEX 6248 X 

 

The ‘X’ suffix in the Certificate Number highlights the variation in 
ambient temperature at the higher power usage. Do not open 
while energized. 

 

  

Notified Body   

LCIE Paris – Head Office

 

33, avenue du General Leclerc  
92260 Fontenay-aux-Roses 
France

 

Notified body number: 

0081  

 
(See attached ATX Declarations for Enclosure, internal  
components and assembly) 
 
 

IMPORTANT  
 

1. 

Read this leaflet carefully before commencing to use the transformer 
and retain it for future use. 

2. 

Check the rating label to ensure the transformer is suitable for the 
supply provided, ambient temperature present and IP rating. 

3. 

The transformer housing is constructed from GRP (Glass Reinforced 
Polyester) and the mounted sockets are plastic, the end user must 
ensure that these materials are suitable for the atmosphere the 
transformer will be used in. Excessive force should not be used on 
plastic components. 

4. 

The transformer must not be opened when energized, even after 
disconnection from the mains supply a delay of 5 minutes should be 
observed before opening. 

5. 

Ensure all replacement fuses are of the correct type and current rating. 

6. 

Prices and design are subject to alteration without notice. All products 
sold are subject to our conditions of sale. A copy of these instructions 
with any relevant revisions can be found at www.wolf-safety.co.uk 

 

INSTALLATION 
 

1. 

The transformer is designed to run a maximum load of 400VA, if this is 
exceeded the internal output fuse may blow.  Any apparatus operated 
from the transformer should be checked to ensure that the maximum 
load is not exceeded. 

2. 

Apparatus with long cable lengths (>20m) must be checked to ensure 
the calculated voltage drop will not prevent the apparatus from operating 
within the specified voltage tolerance (+ 6%-10%). 

3. 

All transformers have terminal blocks suitable for up to 4mm

2

  live, 

neutral and earth. Only one conductor should be fitted to each terminal 
block, for screwed type terminal blocks all terminals should be fully 
tightened down whether a conductor is fitted or not. 

4. 

Approved cable glands must be used and be suitable for the type of 
cable used. Any unused cable entries should be blanked off with an 
approved stopper plug to maintain a minimum IP rating as marked on 
the certification label. 

 

MAINTENANCE 
 

1. 

Isolate the transformer from the mains and wait 5 minutes before 
opening. 

2. 

It is essential that all transformers are maintained in accordance with 
the requirements of EN60079-17 

3. 

A visual check should be carried out to ensure all internal cable is in 
good condition, and not suffering any sign of damage or degradation. 
All internal connections should be checked to ensure that they are 
correctly secured. 

4. 

The condition of the gaskets on the GRP enclosure should be 
inspected to ensure there is no breakdown in the IP66 rating. 

5. 

If changing the input or output fuse care should be taken to replace 
with the correct type of fuse and secure the screwed cover on fully.  

6. 

IMPORTANT.  

No modifications are permitted to the transformer,  

7. 

IMPORTANT.  

Use only genuine Wolf replacement parts.  

 
 

DISPOSAL OF WASTE MATERIAL

 

 

Disposal of packaging, transformer and associated parts should be carried 
out in accordance with national regulations.

 

 

Harmonised standards applied:  
EN50014(1997) Amend. 1 & 2, EN50018(2000), EN50019(2000), 
EN50020(2002), EN50028(1987), EN50281-1-1(1998) 
 
Ingress protection level: 

IP66 

 

 
 

 
 
 
WARNING:  USE ONLY GENUINE WOLF REPLACEMENT PARTS. 
 

Spares list:- 
 

LL-370    Input fuse 10 Amp (am) 
LL-371    Output Fuse 25Amp (am) 
LL-376    230/110 input - 24v output Transformer 
LL-378    24volt ATX socket 

 
Further spares are available on request. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 