Commissioning
54 | WOLF GmbH 3066501_201910
Values are within the values of
:
✔
pump pressure is acceptable.
► End
emissions test mode.
► Remove the oil pressure gauge.
► Fit casing.
i
If the stage 2 or stage 1 pump pressure was adjusted, the CO
2
must be configured and tested
).
6.7.5
Testing the CO
2
levels with the casing closed
► Fit casing.
► Select
parameter HG47
in the contractor level (BM-2) or the contractor menu (AM).
Stage 1:
► Measure the value.
Table 6.3 Set value with casing closed
► Exit
parameter HG47
.
► Select
parameter HG49
and repeat measurement.
HG
Casing closed
CO
2
max.
O
2
min.
CO level max.
47
Stage 1
13.5 %
2.7 %
50 ppm
49
Stage 2
13.5 %
2.7 %
50 ppm
Table 6.3 Set value with casing closed
CO
2
levels increase beyond CO
2
max.:
► Check balanced flue.
Measurements acceptable:
► Exit
parameter HG49
.
► Enter flue gas values in
► Remove the test probe.
► Close the test port. When doing so, ensure the caps are seated firmly!
6.8
Commissioning cascade
BM-2 programming unit installation and operating instructions for contractors
AM display module installation and operating instructions for contractors
KM-2 cascade module installation and operating instructions for contractors
6.8.1
Setting the eBus address in the programming unit or display module
NOTE
Duplicated eBus address!
System faults.
► Assign the eBus address once.
Address 1 is assigned as standard for all heat generators.
► Select
parameter HG10
in the contractor level (BM-2) or the contractor menu (AM) of each heat
generator.
► Assign addresses 1 to 4.
6.8.2
Check that the flue gas damper is functioning properly
► Set
parameter HG13
(input 1) to
Fl. gas damper
.
► Set
parameter HG14
(output 1) to
Fl. gas damper
.
► Check that the flue gas damper opens during operation.
► Disconnect E1 for two minutes during operation (see wiring diagram
).
✔
The heat generator will deactivate and be locked out with fault code 8.
✔
The fan will continue to run at a low speed.
► Reconnect E1.
► Acknowledge fault message.
► Check that the flue damper closes when the system is on standby.