Wolf ATEX 400VA Operation And Maintenance Instructions Download Page 1

LL-366 Issue 8

 

 

 

DF378

 

 

 

 
 

 
Wolf ATEX 400VA GRP Transformer  
Operation and Maintenance Instructions

  

Please Retain – Read Before Use 

Models 
LL-114, LL-114/RIG, LL-114/RB, LL-114/CEAG,  
LL-214, LL-214/RIG, LL-214/RB, LL-214/CEAG, LL-221 
LL-114/ (Suffix defines cable and plug options) 
LL-214/ (Suffix defines cable and plug options) 

 

 
This Wolf ATEX Transformer has a durable GRP enclosure housed in a 
stainless steel skid, within the enclosure is a transformer component with 
maximum load of 400 VA.  The Transformer is approved as Group II 
equipment for use in zone 1 & 2 potentially explosive gases, vapours, mists 
and dusts where the T3 temperature class permits.  

 

 
Approval Codes/Certification:  

 

II 2 GD Ex ed IIC T3 IP66  

 

 

  Ex tD A21 T200ºC  

(Tamb = -20 to +55ºC)  
 
Supply Voltage: 230VAC or 6%, -10%  

 

Output Voltage: 110VAC or 24VAC 
Check equipment label for confirmation of exact rating.

 

 

Certificate ‘X’ suffix - Do not open Transformer while energized.  

 

Notified Body   

LCIE Paris – Head Office

 

33, Avenue du General Leclerc  
92260 Fontenay-aux-Roses 
France

 

Notified body number: 

0081  

 
See attached ATX EC Declaration of Conformity. 
 

IMPORTANT  
 

1. 

Read this leaflet carefully before commencing to use the Transformer 
and retain it for future use. 

2. 

Check the rating label to ensure the Transformer is suitable for the 
supply provided, ambient temperature present and IP rating. 

3. 

The Transformer housing is constructed from GRP (Glass Reinforced 
Polyester) and the mounted sockets are plastic, the end user must 
ensure that these materials are suitable for the atmosphere the 
transformer will be used in. Excessive force should not be used on 
plastic components. 

4. 

The Transformer must not be opened when energized, even after 
disconnection from the mains supply a delay of 5 minutes should be 
observed before opening. 

5. 

Ensure all replacement fuses are of the correct type and current rating. 

6. 

Prices and design are subject to alteration without notice. All products 
sold are subject to our conditions of sale. A copy of these instructions 
with any relevant revisions can be found at www.wolf-safety.co.uk 

 

USE OF ATEX TRANSFORMERS 
 

1. 

The Transformer is designed to supply a maximum load of 400 VA, if 
this is exceeded the internal output fuse may blow.  Any apparatus 
operated from the transformer should be checked to ensure that the 
maximum load is not exceeded. 

2. 

The fuse ratings used in this Transformer have been selected for use 
with Wolf temporary lighting products.  For the fuses to provide the 
required level of protection the output cable to any connected device 
must be limited to a maximum 35 metres of 4mm

2

 cable or 20 metres of 

2.5mm

2

 cable. Longer cable lengths and smaller cable diameters will 

increase cable impedance; this may prevent correct fuse operation, 
resulting in overheating, damage to the Transformer and a potentially 
unsafe condition in the safe or hazardous area. 

3. 

It is the user’s responsibility to ensure that any cable configuration used 
with this Transformer will not compromise the integral fuse protection of 
the unit.   

4. 

Apparatus with long cable lengths (>20m) must be checked to ensure 
the calculated voltage drop will not prevent the apparatus from operating 
within the specified voltage tolerance (+ 6%, -10%). 

5. 

All Transformers have terminal blocks suitable for up to 4mm

2

 live, 

neutral and earth. Only one conductor should be fitted to each terminal 

block, for screwed type terminal blocks all terminals should be fully 
tightened down whether a conductor is fitted or not. 

6. 

Approved cable glands must be used and be suitable for the type of 
cable used. Any unused cable entries should be blanked off with an 
approved stopper plug to maintain a minimum IP rating as marked on 
the certification label. 
 

MAINTENANCE

 

 

1. 

Isolate the Transformer from the mains and wait 5 minutes before 
opening. 

2. 

It is essential that all Transformers are maintained in accordance with 
the requirements of EN60079-17 

3. 

A visual check should be carried out to ensure all internal cable is in 
good condition, and not suffering any sign of damage or degradation. 
All internal connections should be checked to ensure that they are 
correctly secured. 

4. 

The condition of the gaskets on the GRP enclosure should be 
inspected to ensure there is no breakdown in the IP66 rating. 

5. 

If changing the input or output fuse care should be taken to replace 
with the correct type of fuse and secure the screwed cover on fully.  

6. 

IMPORTANT.  

No modifications are permitted to the Transformer,  

 
 

DISPOSAL OF WASTE MATERIAL

 

 

Disposal of packaging, Transformer and associated parts should be carried 
out in accordance with national regulations.

 

 
Ingress protection level: 

IP66 

 

 
 
WARNING:  USE ONLY GENUINE WOLF REPLACEMENT PARTS. 
 

Spares list:- 

Input 

Voltage 

Input 
Fuse 

Wolf Part 

Number 

Output 

Voltage 

Output 

fuse 

Wolf 

Part 

Number 

110V 4Amp 

(aM) 

LL-377 24V 

16Amp 

(gG) 

LL-379 

230V 2Amp 

(aM) 

LL-1002 24V 

16Amp 

(gG) 

LL-379 

230V 2Amp 

(aM) 

LL-1002 110V 

4Amp 

(gG) 

LL-

1007 

  
LL-376    230/110 input - 24v output 400VA transformer component. 
LL-378    24 volt ATX socket. 
 
Further spares are available on request. 
 
 