PM.2.004922.EN - 810-000-000 SRS DC-PWM

©

   · Edition 22 July 2020

CONTROLLER SOFTWARE UPGRADE

• 

Connect the handset to the RJ45 connector

• 

If necessary, using keys 

ã

 and 

ä

 choose the required language and confirm with the “OK” key

• 

Using keys 

ã

 and 

ä

, run through the MAIN MENU and choose “UPDATE”

• 

Press “OK” to confirm the choice

• 

Display shows the last available update and the software version in use at the moment.

• 

Press “OK” to confirm the software update

• 

Controller operates a reset and the display shows “Upload” with the progression value of data loading

• 

At the end of the upload the controller operates a reset

• 

It is anyway advisable to SET FACTORY DEFAULT from the PROFILE SETTINGS menu and to run a new SELF-LEARNING CYCLE, 

checking the parameter settings.

In case of interruption of connection between handset and controller during the data transfer, turn “off” the controller, turn it “on” again 

and reconnect the handset.The upload starts again from the beginning

.

10 

DOOR OPERATOR MAINTENANCE

At least once a year complete the following checks:

• 

Clean the doors (tracks, bottom tracks, belts etc.) from dust or debris as this maintains the door good mechanical operation

• 

Check the electric connections and their fitting to the connectors

• 

Check that the door operator toothed belt is tight enough and in good working condition 

• 

Check and clean the cable connections of the motor and of the motor Encoder

11 

SPARE PARTS

It is possible to order all the Sematic Drive System© spare parts using the spare parts catalogue, by specifying the required quantity and 

the code of the ordered piece.

The spare parts manual is extremely important to avoid misunderstandings and to ensure a rapid supply of the correct spare parts. The 

spare parts catalogue, with photographs and details will make the Sematic doors spare parts purchase easy and quick

.

Summary of Contents for sematic SRS DC-PWM

Page 1: ...ittur com Copyright WITTUR 2020 SRS DC PWM Drive No part of this publication may be reproduced or translated even in part without prior written permission from WITTUR Subject to change without notice...

Page 2: ......

Page 3: ...Instruction with handset 15 6 5 Closing Rest type Instruction with handset 16 6 5 1 Motor on default 16 6 5 2 Motor off 16 6 5 3 PM activation Delay Default 300 sec 16 6 5 4 PM Opening space Default...

Page 4: ...8 5 2 SKATE TYPE select by keypad 23 8 5 4 CLOSING REST TYPE select by keypad 23 8 5 5 MOTOR select by keypad 23 8 5 6 MAX CURRENT END CH select by keypad 23 8 5 7 LA THRESOLD 24 8 6 Maintenance Menu...

Page 5: ...e disclosed to anyone without Sematic s written consent apart from authorized representatives employed by the user which commits itself to the confidentiality clause The Company that makes use of the...

Page 6: ...omatic lift doors Frame and frameless glass doors Enhanced car door operator solutions Complete cabins Car Frames Custom integrated packages Special lift doors cabins and car frames ELEVATOR SYSTEMS S...

Page 7: ...n ensured 1 Quality control of raw material supply 2 Process control 3 Product control 4 Conformity tests according to Sematic specifications Furthermore Sematic guarantees the performance life of its...

Page 8: ...45 plug The handset 7 is a key pad that allows viewing and modification of the function parameters stored in the controller It is important to use the Sematic handset for installation or maintenance a...

Page 9: ...DC PWM Edition 22 July 2020 2 1 SPEED PROFILE 9 Opening cycle O1 Opening low speed O2 Opening hight speed Closing cycle C1 Closing low speed C2 Closing hight speed Key Ka Door opening Kc Door closing...

Page 10: ...60 C HUMIDITY non condensing between 20 and 80 PROTECTION rapid cartridge fuse 5x20 4 A PERFORMANCE SPEED separately adjustable for opening and closing through regulation trimmers REVERSAL SENSITIVIT...

Page 11: ...om Changes can be made without notice PM 2 004922 EN 810 000 000 SRS DC PWM Edition 22 July 2020 4 SIGNALS TO FROM THE DOOR CONTROLLER 4 1 CONNECTIONS 1 Safety chains 2 Main Lift Controller 3 Photocel...

Page 12: ...input signal Voltage from the Main Lift Controller range from 6 to 24 V CC To use this feature Remove the link between terminals 37 38 Connect terminal 37 to the external input signals power source 0V...

Page 13: ...utput signal from a photocell or similar device formed by a voltage free contact so that the door controller will directly receive the command to re open The photocell or similar device has therefore...

Page 14: ...signal loss or failure of the main lift controller the door controller immediately stops the door movement Note in manual mode the main lift controller signals are not active if CLS or OPN switches ar...

Page 15: ...of the doors in low speed forced closing by closing the 15 22 connector pins using a relay voltage free contact 6 3 MOTOR ROTATION DURING CLOSING This function fixes the motor rotation during the clo...

Page 16: ...position error Default 5 mm This sub parameter represents the space threshold with relation to the open skate parking point represented by the PM ACTIVATION DELAY parameter within which the panels can...

Page 17: ...and waits for external manitenan ce cod 05 5 flashes pause Encoder jerk Interruption of the motor s Encoder cables or interruption of the motor cables after system s start up or the connecting plug t...

Page 18: ...losing signal is given for instance after power supply interruption it performs a reset cycle i e it searches for a closing limit at low speed not a self learning cycle 7 2 SELF LEARNING CYCLE PROCEDU...

Page 19: ...speed turn ing it clockwise will set the high closing speed from the minimum speed value to the maximum speed value LW CLS trimmer sets the low closing speed turn ing it clockwise will set the low cl...

Page 20: ...icture 3 a 16 mm diameter hole is required in any chosen position within the Car walls Note when the handset is connected to the controller the display shows the warrantly expiration date 2 years from...

Page 21: ...ittur com Changes can be made without notice PM 2 004922 EN 810 000 000 SRS DC PWM Edition 22 July 2020 8 2 USER HANDSET MENUS AND SUBMENUS Closing Rest type Max current end CL LA Threshold Final low...

Page 22: ...confirm the option On the display the following options are viewed High speed OP XX Low speed OP XX High speed CL XX Low speed CL XX Revers force XX N Acc AP Dec AP Acc CH Acc CH Using keys and to ru...

Page 23: ...osed skate Open skate Using keys and select the required option and press Ok to confirm Keeping the same values on the screen press OK to confirm the following options PM ritardo attivazione PM apertu...

Page 24: ...ave been performed in this working time and the manufacture date The following options are available BACK Press key F1 to restore the menu Maintenance MENU Press key F3 to restore the Main Menu If the...

Page 25: ...available BACK Press key F1 to restore the menu MAINTENANCE MENU Press key F3 to restore the MAIN MENU The access to the MANUFACTURER MENU is reserved protected by password If the option SET FACTORY...

Page 26: ...between handset and controller during the data transfer turn off the controller turn it on again and reconnect the handset The upload starts again from the beginning 10 DOOR OPERATOR MAINTENANCE At le...

Page 27: ......

Page 28: ...YOUR GLOBAL PARTNER FOR COMPONENTS MODULES AND SYSTEMS IN THE ELEVATOR INDUSTRY More information about Wittur Group available on line a WITTUR brand a WITTUR brand a WITTUR brand...

Reviews: