WITA go.future LED  40-XX Operating Instructions Manual Download Page 1

NUR ORIGINAL MIT DER RAUTE®

WITA go.future LED 40-XX | 60-XX

ORIGINAL EINBAU- UND 
BETRIEBSANLEITUNG

SEITE 2–19

TRANSLATION OF THE ORIGINAL INSTALLATION 
AND OPERATING INSTRUCTIONS

PAGE 20–37

TRADUCTION DES INSTRUCTIONS DE MONTAGE
ET DE SERVICE ORIGINALES

PAGE 38–55

|

www.wita.de

EEI

0,20

D

GB

FR

Summary of Contents for go.future LED 40-XX

Page 1: ...40 XX 60 XX ORIGINAL EINBAU UND BETRIEBSANLEITUNG SEITE 2 19 TRANSLATION OF THE ORIGINAL INSTALLATION AND OPERATING INSTRUCTIONS PAGE 20 37 TRADUCTION DES INSTRUCTIONS DE MONTAGE ET DE SERVICE ORIGIN...

Page 2: ...Unzul ssige Betriebsweisen 8 3 Transport und Lagerung 8 4 Bestimmungsgem e Verwendung 8 5 Angaben ber das Erzeugnis 9 5 1 Technische Daten go future LED 40 9 5 2 Technische Daten go future LED 60 10 5...

Page 3: ...t tserkl rung bezieht mit den folgenden Normen und Richtlinien bereinstimmen Elektromagnetische Vertr glichkeit Richtlinie 2014 30 EU EN 55014 1 2006 A1 2009 A2 2011 EN 55014 2 1997 A1 2001 A2 2008 EN...

Page 4: ...se zu beachten sondern auch die in den an deren Abschnitten genannten speziellen Sicherheitshinweise Dieser Anleitung ist eine Kopie der EU Konformit tserkl rung beigef gt Bei einer mit uns nicht abge...

Page 5: ...fweisen Verantwor tungsbereich Zust ndigkeit und berwachung des Personals sind durch den Betreiber sicherzustellen Sollte das Personal nicht die erforderlichen Kenntnisse aufweisen so ist dieses entsp...

Page 6: ...keiten in Folge eines Lecks Versagen vorgeschriebener Reparatur und Wartungsarbeiten 2 5 Sicherheitsbewusstes Arbeiten Die in dieser Anleitung aufgef hrten Sicherheitshinweise und auch die bestehenden...

Page 7: ...ziertem Fachper sonal vorgenommen werden Sie m ssen sich vorher anhand der Bedienungsanleitung mit dem Produkt vertraut gemacht haben Arbeiten an der Pumpe sind grunds tzlich nur im Still stand der A...

Page 8: ...ngt einzuhalten 3 Transport und Lagerung Das Produkt ist sofort nach Erhalt auf etwaige Transportsch den hin zu untersuchen Sollten Transportsch den festgestellt werden so sind diese beim Spediteur ge...

Page 9: ...10 Umgebungstemperatur 0 C bis 40 C Medientemperatur 5 bis 110 C Systemdruck Max 10 bar 1 MPa Zugelassene F rdermedien Heizungswasser nach VDI 2035 Wasser Glykolgemische 1 1 Zulaufdruck zul ssiger Ein...

Page 10: ...sche 1 1 Zulaufdruck zul ssiger Einsatzbereich Vorsicht Unzul ssige F rdermedien k nnen die Pumpe zerst ren sowie Personensch den hervorrufen Unbedingt Herstellerangaben und Sicherheitsdatenbl tter be...

Page 11: ...go future LED kann der Energieverbrauch gegen ber einer herk mmlichen Umw lzpumpe bis ca 80 gesenkt werden Die hydraulische Leistung konnte gegen ber den Standardpumpen nahezu gleichgehalten werden D...

Page 12: ...en Jedes Mal wenn der Taster bet tigt wird ndert sich die Pumpeneinstellung Durch siebenmaliges Dr cken werden alle Einstellungen einmal durchlaufen Leuchtfeld Beschreibung I Konstantdrehzahlstufe I I...

Page 13: ...t werden Falls die Heizungsanlage zu wenig W rme an die Heizk rper abgibt ist zu kontrollieren ob die automatische Nachtabsenkung aktiviert ist Gegebenenfalls ist die automatische Nachtabsen kung zu d...

Page 14: ...temperatur dann aktiviert sich die automatische Nachtabsenkung ebenso nach einem Stromausfall 9 Montage Fig 1 Spannungsfreie Montage mit waagerecht liegendem Pumpenmotor durchf hren Richtungspfeil auf...

Page 15: ...ssen Stromart und Spannung m ssen den Angaben des Typenschildes entsprechen Vorschriften der lokalen Energieversorger beachten Unfallverh tungsvorschriften beachten Niemals am Netzkabel ziehen Kabel n...

Page 16: ...tungen sind Aderendh lsen zu benutzen 11 Anlage f llen und entl ften Anlage sachgerecht f llen und entl ften Um die Pumpe zu entl ften sollte die Elektronik auf Stufe III gestellt werden und f r minde...

Page 17: ...fen linkes Anzeigefeld der Leistungsanzeige blinkt im Sekundentakt m gliche Ursache Fehler in der Spannungsversorgung Luft in der Anlage Schieber geschlossen Luft im System Pumpenleistung zu hoch Luft...

Page 18: ...Taste dr cken oder Pumpe mindestens 1 Minute vom Netz trennen Besteht der Fehler weiterhin muss die Pumpe er setzt werden Pumpe spannungsfrei schalten und gegen Wieder einschalten sichern Wenn m glic...

Page 19: ...nzelteile geh ren nicht in den Hausm ll sondern m ssen umweltgerecht entsorgt werden Nehmen Sie hierf r bitte die ffentlichen oder privaten Entsorgungsgesellschaften in Anspruch Im Downloadbereich uns...

Page 20: ...spare parts 25 2 9 Unpermitted operation 26 3 Transport and Storage 26 4 Intended Use 26 5 Information About the Product 27 5 1 Technical data go future LED 40 XX 27 5 2 Technical data go future LED 6...

Page 21: ...EC Declaration of Conformity refers ful l the following standards and guidelines Electromagnetic Compatibility Directive 2014 30 EU EN 55014 1 2006 A1 2009 A2 2011 EN 55014 2 1997 A1 2001 A2 2008 EN...

Page 22: ...under section 2 and the special safety instructions detailed in the other sections A copy of the EC Declaration of Conformity is provided with these instructions This declaration shall be deemed void...

Page 23: ...vant quali cations Areas of responsibility and monitoring of personnel must be guaranteed by the owner operator If personnel do not have the necessary know how they must be trained or instructed accor...

Page 24: ...ting from a leak Failure of prescribed repair and maintenance work 2 5 Safety conscious working Observe the safety instructions detailed in this manual along with the current national accident prevent...

Page 25: ...advance with the product using the operating instructions Conducting work on the pump is only permitted when the system is shut down Ensure that the device is securely disconnected from the power sup...

Page 26: ...roduct inspect it immediately for damage caused in transport Should you detect any transport damage assert a claim with the haulier Incorrect transport and storage can lead to personal injury or damag...

Page 27: ...perature 0 C to 40 C Media temperature 5 to 110 C Max systeme pressure 10 bar 1 MPa Permitted pumping media Heating water according to VDI 2035 Water glycol mixture 1 1 Inlet pressure Permissible rang...

Page 28: ...ol mixture 1 1 Inlet pressure Permissible range of application Caution Unpermitted pumping media can destroy the pump and cause perso nal injury Observe the manufacturer s information and safety data...

Page 29: ...y index of 0 20 The go future LED pump can reduce energy consumption by up to 80 compared to a standard circulation pump whilst maintaining the same level of hydraulic power The pump output can be adj...

Page 30: ...ion button Each time the button is pressed the pump setting changes By pressing seven times all settings are run through once Illuminated panel Description I Constant speed level I II Constant speed l...

Page 31: ...tic night economy If the heating system supplies too little heat to the radiators check whether automatic night economy is activated If so deactivate the automatic night economy function The following...

Page 32: ...increases the automatic night economy function then activates itself as well as after a power failure 9 Installation Fig 1 Carry out voltage free mounting with the pump motor in a horizontal position...

Page 33: ...al energy Only have installation and electrical connection performed by a specialist and in line with the valid regulations e g IEC VDE etc The current type and voltage must correspond with the inform...

Page 34: ...ferrules if using ne wire cables 11 Filling and bleeding the system The system must be lled and bled correctly To vent the pump the electronics should be set to level III and run in this position for...

Page 35: ...of scalds Error indication or Error code in the display of the pump The pump do not deliver Display do not light the pump is running but not water supply Noises in the system Pump is making noises Bui...

Page 36: ...e Rotor blocked Overload Electronic error remedy If possible remove the over ow valve discharge valve or close it check the power supply check the power supply Press any key or disconnect the pump for...

Page 37: ...of the pump and or individual parts in household waste Dispose of the pump and or parts in an environmentally conscious way To do this please contact a public or private disposal organisation A list o...

Page 38: ...sation 43 2 9 Modes d utilisation non autoris s 44 3 Transport et stockage 44 4 Utilisation conforme 45 5 Informations sur le produit 45 5 1 Caract ristiques techniques go future LED 40 XX 45 5 2 Cara...

Page 39: ...ette d claration de conformit europ enne sont en conformit avec les normes et les directives suivantes Directive compatibilit lectromagn tique 2014 30 EU EN 55014 1 2006 A1 2009 A2 2011 EN 55014 2 199...

Page 40: ...ais aussi les consignes de s curit particuli res gurant dans les autres sections Les pr sentes instructions de service sont accompagn es d une d claration de conformit europ enne Toute modi cation eff...

Page 41: ...enu de xer les responsabilit s et comp tences du personnel et il doit pr voir des contr les Si le personnel ne dispose pas des connaissances requises il doit tre form ou initi conform ment aux besoins...

Page 42: ...paration et d entretien prescrits 2 5 Travail respectueux de la s curit Les consignes de s curit contenues dans ces instructions de service ainsi que les prescriptions nationales de pr vention contre...

Page 43: ...rsonnel sp cialis et quali Le personnel doit lire les instructions de service avant de commencer les travaux a n de se familiariser avec le produit Les travaux sur la pompe sont uniquement autoris s l...

Page 44: ...assur e lorsqu elle est utilis e de mani re conforme sa destination Pour cela observer le point 4 de ces instructions de service Les valeurs limites indiqu es dans les caract ristiques techniques doiv...

Page 45: ...00 l h Puissance consomm e PI W 3 23 Tension d alimentation 1 x 230V 50Hz Niveau de pression acoustique des missions 40 dB A EEI 0 20 Type de protection IP 42 Temp rature ambiante TF 110 Temp rature a...

Page 46: ...ion Domaine d utilisation autoris Attention L utilisation de uides de refoulement non autoris s peut entra ner la destruction de la pompe ainsi que des blessures Toujours respecter les informations du...

Page 47: ...re la consommation d nergie de 80 environ par rapport une pompe de cir culation traditionnelle La puissance hydraulique a pu tre maintenue au m me niveau que celle des pompes standard La puissance de...

Page 48: ...bes de la pompe Le r glage de la pompe change chaque fois que le bouton est actionn Appuyer sept fois pour parcourir tous les r glages Champ d allumage Description I Niveau de vitesse constante I II N...

Page 49: ...ivent jamais tre r gl es sur l abaissement nocturne automatique Si l installation de chauffage transmet trop peu de chaleur au radiateur contr ler si l abaissement nocturne automatique est activ Il fa...

Page 50: ...nt nocturne s active C est galement le cas apr s une panne de courant 9 Montage Fig 1 R aliser le montage sans contrainte le moteur de la pompe doit tre mont horizontalement la che du sens de rotation...

Page 51: ...on doivent correspondre aux indications de la plaque signal tique Respecter les prescriptions des compagnies d nergie comp tentes Respecter les prescriptions de pr vention contre les accidents Ne jama...

Page 52: ...1 Remplissage de l installation et purge Remplir et purger l installation comme il se doit Pour purger la pompe l lectronique doit tre r gl e sur le niveau III et fonctionner pendant au moins 20 minut...

Page 53: ...onctionne mais ne d bite pas d eau Bruits dans l installation La pompe fait du bruit Le b timent ne se r chauffe pas Aucun r glage automatique du d bit dans les paliers de pression Cause possible Erre...

Page 54: ...rature de l installation Appuyer sur une touche quelconque ou d brancher la pompe du r seau pendant au moins 1 minute Si le d faut persiste remplacez la pompe Mettre la pompe hors tension et s curise...

Page 55: ...ne doivent pas tre jet es avec les ordures m nag res mais doivent tre limin es de mani re respectueuse de l environnement Pour ce faire veuillez vous adresser aux soci t s de collecte des d chets publ...

Page 56: ...hel wita com pl biuro hel wita com Stand 11 2017 Produktionsbedingte Abweichungen in Ma en und Ausf hrungen behalten wir uns vor Irrtum und technische nderungen vorbehalten As of 11 2017 Production r...