SFC Machine Interface (SMI 2) Installation Manual
1146400
Chapter 2
– Installation
27
Connecting Machine Inhibit Output Wiring
To make wiring connections for the machine inhibit output circuit, do the following, referring to
Figure 2-7, page 23, and Figure 1, SFC Machine Interface 2 Wiring Diagram, at the end of this
manual. Make sure to number all wires in a way consistent with your machine’s electrical prints.
1.
Determine how you will run the wires from your machine control to the SMI 2 control board
outputs. Refer to your machine control manual or other electrical prints. You need two wires for
the machine inhibit circuit.
2.
Run the machine inhibit circuit wires to SMI 2 through flexible liquid tight conduit to the
knockout at the bottom center of the SMI 2 enclosure or to the appropriate location on your
console. If you ordered the enclosure, it is rated NEMA 12 (protected against dust and oil), and
you must use NEMA-12-rated conduit and make proper connections to ensure NEMA 12
protection.
3.
Connect the wires for the machine inhibit circuit to pins 4 and 5 on connector TB5 (see Figure
2-7, page 23), and Figure 1, SFC Machine Monitor 2 Wiring Diagram, at the end of this manual.).
This output is a dry-contact (4A Max @ 240 VAC or 30 VDC).
Connecting SMI 2 to Your Ethernet
NOTICE
To use the optional wireless connection, see
Error! Reference source not found.
, page
Error!
Bookmark not defined.
.
To wire the SMI 2 to your Ethernet, do the following:
1.
Run an Ethernet cable through flexible liquid tight conduit into the knockout at the center bottom
of the SMI 2 enclosure or to the appropriate location on your console. If you ordered the
enclosure, it is rated NEMA 12 (protected against dust and oil), and you must use NEMA-12-
rated conduit and make proper connections to ensure NEMA 12 protection.
2.
Plug the Ethernet cable into the Ethernet connector (“network jack”) near the center of the SMI 2
control board. Figure 2-6, page 22.
Checking Wiring Connections
Before using SMI 2, perform the following checks to make sure that you have wired the unit
correctly.
Checking Power Connections
To check SMI 2 power connections, do the following:
1.
If you have an SMI 2 enclosure, connect AC wires from the enclosure to the power source. If you
have an SMI 2 panel mount, make sure that your AC power supply is connected.
2.
Turn on power to SMI 2. The SMI 2 Main Menu, shown in Figure 2-8, should display.
Summary of Contents for ShopFloorConnect SMI 2
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 14: ......
Page 32: ...1146400 SFC Machine Interface SMI 2 Installation Manual 32 Chapter 2 Installation ...
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......