AutoSet User Manual
1137200
Installation
2-25
5.
Remove the AutoSet firmware chip, and replace it with a new chip.
The chip, which has a label on it, is identified as component “XU106” and is located
directly beneath the power transformer (T101) at the top of the AutoSet processor board.
Note that the semi-circular notch on the firmware chip faces to the left. When replacing
the chip, make sure that the notch on the new chip also faces to the left.
6.
If you have not installed a zero cam switch and wired a zero cam input to your AutoSet,
wire the SmartPAC 2 zero cam output (pin #248 on terminal block TB107 on the
SmartPAC 2 processor board) to the AutoSet zero cam input (pin #2 on TB101A or
TB101B on the AutoSet processor board). Also, connect a ground wire from pin #250 on
TB107 to pin #10 on TB101A or pin #5 on TB101B. You can run the zero cam wiring
through the same conduit as the communications wiring used in step 2.
7.
Power up SmartPAC 2.
8.
Select TONNAGE MONITOR on the Main Initialization Menu to display the Tonnage
Monitor Initialization Menu.
9.
Select INITIALIZE PARAMETERS on the Tonnage Monitor Initialization Menu. Press
ENTER when the warning message displays to confirm that you want to continue with
initialization.
10.
Set the capacity of your press on the Tonnage Monitor Initialization Menu, and enable or
disable the repeatability setpoint, the startup counter, and setup mode.
11.
Select SECURITY ACCESS on the Tonnage Monitor Initialization Menu, and configure
AutoSet security the way you want it.
12.
When you are ready to make parts, go to Program mode and enter setpoint percentages
and a sample period setting for each programmed tool, referring to your SmartPAC 2 user
manual for assistance.
13.
Return the old AutoSet firmware chip to Wintriss.
Connecting an AutoSet to SmartPAC 1
To connect an AutoSet to a SmartPAC 1 control, perform the following steps, referring to
your SmartPAC user manual for help:
1.
Access the List of Installed Options screen on the Main Initialization Menu, and verify the
version number of SmartPAC and of Character Generator.
•
If SmartPAC firmware is earlier than V1.56, you must replace it with a current version.
•
If Character Generator is earlier than V1.07, you must replace it with version V1.07.
Contact Wintriss Tech. Support to arrange for updated firmware.
2.
If you must replace SmartPAC firmware, be sure to record the settings for start and stop
time limits on the Set Brake Monitor screen in Initialization mode. Also, record the cam
channel names shown on the Cam Channel Name Menu in Initialization before changing
the firmware. Refer to your SmartPAC manual for assistance.