INSTALLATION INSTRUCTIONS

DSE 890 WebNet® GATEWAY

This instruction sheet is provided in assisting in the installation of the DSE890 

module.  For a complete DSE installation and operation manual please go to 

DSE website @ www.deepseaplc.com.  Document # 057-165.

RS485 CONNECTOR

This socket provides support for connection to a maximum of 32 (thirty two) DSE 

controllers in a daisy chain RS485 network. 

Ensure termination resistors (120Ω) are fitted as shown to the ends of the link as per 

RS485 standard.

PIN No.

NOTES

A (-)

Two core screened twisted pair cable.

120 Ω impedance suitable for RS485 use.

Recommended cable type - Belden 984

Max distance 200m (.2km) when using Belden 984 or direct equiv-

alent.