Installation and operating instructions Wilo-SiFire Easy
43
3.1 Residual risk during transport and storage
WARNING! Risk of cuts!
Sharp edges or any not protected threaded parts
entail the risk of getting cut.
Take necessary cautions to avoid injuries and
use protective equipment (wear protective
gloves).
WARNING! Risk of personal injury!
Do not stand or put members under the sus-
pended parts during handling and installation.
Use protective clothing to prevent accidents
(wear helmet and safety shoes).
WARNING! Risk of impact!
Be careful of prominent parts and parts at head
level. Use protective clothing to prevent acci-
dents.
DANGER! Risk of fall!
Prohibit access to wells or tanks, where pumps
are installed. Wells must be covered.
WARNING! Risk of irritation!
During handling, avoid spillage of battery acid
solution which could cause irritations or mate-
rial damage. Use special protections to avoid
contact.
CAUTION! Risk of environmental pollution!
Avoid dumping of oil from the engine or diesel
fuel from the tank. During handling, keep them
flat. Use suitable protection and implement the
necessary measures to prevent pollution of soil,
water, etc.
4 Intended use
The pressure boosting systems for fire extinguish-
ing purposes are designed for professional use.
They are used when an increase of pressure or a
maintaining under pressure of the fire network is
necessary.
The system must be installed in a special room
which is protected from frost and rain, fireproof
and ventilated enough, with necessary spaces
around pumps for movements and regular main-
tenance. The room must be in accordance with the
EN 12845 standards. Airflow for ventilation and
for cooling of engines, more specifically diesel
engine -if present- has to be sufficient.
5 Product data
5.1 Type key
5.3 Scope of delivery
• Pressure boosting system for fire fighting
• Operating instructions for the fire fighting system.
• Operating instructions for the pumps (1 manual
per pump type)
• Operating instructions for the switchgear (1 man-
ual per switchgear type)
• Operating instructions and maintenance of diesel
motor if present.
5.4 Accessories
• Priming tank(s) complete with electrical float;
• Electric contacts limit for check valve of pumps;
• Flexible vibration-damping sleeves;
• Eccentric suction cone kit with vacuum gauge for
suction side of the pumps;
• Butterfly valves;
• Silencer for diesel engine;
Example: SiFire Easy 40/200-180-7.5/10.5 EDJ
SiFire:
Name of the fire fighting system for sprinkler
systems according to EN 12845
40/200:
Type of the pump
180:
Impeller diameter of main pump
7.5/10.5:
Rated power of pumps (kW)-electrical motor/
diesel motor
EDJ:
Configuration
E
: 1 electric pump
D : 1 diesel pump
EJ : 1 electric pump + 1 jockey pump
EEJ : 2 electric pumps + 1 jockey pump
EDJ: 1 electric pump + 1 diesel pump + 1 jockey
pump
DJ : 1 diesel pump + 1 jockey pump
5.2
Technical data
Maximum operating pressure:
10 bar or 16 bar (depending on the pump type)
Maximum ambient temperature:
5 to +40 °C (10 to 40 °C if diesel pump is installed)
Maximum water temperature:
5 to +40 °C
Supply voltage:
3 x 400 V
+
/
-
10% (1 x 230 V
+
/- 10%, for diesel pump switchgear)
Frequency:
50 Hz
Maximum relative humidity:
50% with T.max 40 °C (*)
Protection class of switchgear:
IP54
Protection class of pump:
IP55
Insulation class:
F
Efficiency class:
IE3
Maximum altitude for installation:
1000 m above sea level (*)
Minimum atmospheric pressure:
760 mmHg (*)
Rated current:
refer to the rating plate
(*) Seen the specific graphs and tables in the catalogues and maintenance manuals for the details of class variations for electric and diesel engines with regard to
different temperatures, altitudes, atmospheric pressure, fuel temperature and viscosity compared to standard test conditions.